Access Configuration Manual
Contents
Index
Search
Access
Access 4.x
Access application tool
Searching for controller
Upgrading controller
Manual backup and commissioning report
Manual control
Manual control of the Input/Output
Manual control of the Fans
Manual control of the Heating/Cooling sequences
Manual control of the Actuators
Configuration
Configuration wizard
Temperature control
Temperature controllers
Neutral zone
Control modes
Supply air
Supply air outdoor compensated
Room cascade
Extract air cascade
Room (summer) else supply air
Extract air (summer) else supply air
Room outdoor compensated
Extract air outdoor compensated
Extract air dependent supply air
Heating/Cooling sequences
Starting order of heating/cooling
Starting order of the fan compensation sequences
Configuration examples
Heating (water)
Freeze protection
Heating (electric)
Cooling (water)
Cooling (DX)
Exchanger (rotary)
Rotary exchanger defrosting (temperature monitoring)
Exchanger (plate)
Defrosting
Temperature monitoring defrosting
Pressure monitoring defrosting
Sectional defrosting
Configuration
Calibration
Configuring the DM50-C
Exchanger (liquid)
Reversible HP
Changeover
Fan setpoint compensation
Summer / winter mode
Step controller
Sequential step control
Binary step control
Pretreatment
Cooling recovery mode
Extra controller
External setpoint device
Room controller S-ED-RU-DFO
Preheater
Preheater sub-function: Preheating
Preheater sub-function: Filter drying
Zone control
Zone control: Room cascade configuration example
Fan control
Fan control type
Pressure
Flow
Manual
External
Supply air pressure and extract air fan slave
Supply air pressure with extract air flow slave
Extract air pressure with supply air fan slave
Extract air fan pressure with supply air flow slave
Flow calculation
Fan compensation
Filter monitoring (up to Access 4.5)
Guard type filter monitor
Sensor type filter monitor
Periodic filter replacement
Filter monitoring (in Access 4.6 and later)
Guard type filter monitor
Sensor type filter monitor
Filter calibration
Periodic filter replacement
Humidity control
Humidification
Dehumidification (Separate dehumidification unit)
Dehumidification (Sequence override)
Demand control
Air quality control
Fan start/stop
Mixing damper function
Free cooling
Humidification + Dehumidification
Humidity neutral zone
Support control
Enthalpy control
Dampers
Outdoor damper (Open/Closed)
Exhaust (Open/Closed)
EATR control (Modulated)
Recirculation (Open/Closed)
I/O allocation settings
Digital inputs
DI: Cooling/(Heating) changeover
DI: Lock PID controller supply
DI: Filter guard supply air
DI: Filter guard extract air
DI: Feedback fire damper
Digital outputs
Analog outputs
Analog inputs
AI: External setpoint temperature
AI: Pressure filter supply air
AI: Pressure filter extract air
Extra sensors & inputs
Alarm acknowledgment
Extra sensors
Extra alarm
Extra indications & outputs
Extra time channel
Run indication
Sum alarm output
Auxiliary indication
Temperature output
Energy insight
Power usage fans
Power usage heater
Power recovery exchanger
Heat exchanger efficiency monitoring
Fire/Smoke
Fire mode damper
Smoke detector input (T1)
Fail-safe
Starting and stopping the unit
Extended running
Digital input
Navipad
Room unit
External stop
Communication
Ports
Int-link
BMS
Ext-link
EFX
Connected devices
Modbus Fan
Modbus Pressure transmitter
Modbus Rotary exchanger
Modbus Damper
Modbus Section defrosting module (DM50-C)
EXOline Room unit ED-RUx
Modbus Room unit ED-RUD
Setting up the room unit
Modbus Room unit ED-RUD
Device status
BMS watchdog
Alarms
Reviewing alarms
Alarm history
Alarm snapshot
Configuring alarms
Browsing alarms
Air and temperature control
Extra functions
Extra sensors and alarms
Component malfunction
Manual operation and warnings
Fire/Smoke
Access 5.x
Access application tool
Searching for controller
Upgrading controller
Manual backup and commissioning report
Manual control
Manual control of the Input/Output
Manual control of the Fans
Manual control of the Heating/Cooling sequences
Manual control of the Actuators
Configuration
Configuration wizard
Temperature control
Temperature controllers
Neutral zone
Control modes
Supply air
Supply air outdoor compensated
Room cascade
Extract air cascade
Room (summer) else supply air
Extract air (summer) else supply air
Room outdoor compensated
Extract air outdoor compensated
Extract air dependent supply air
Heating/Cooling sequences
Starting order of heating/cooling
Starting order of the fan compensation sequences
Configuration examples
Heating (water)
Freeze protection
Heating (electric)
Cooling (water)
Cooling (DX)
Exchanger (rotary)
Rotary exchanger defrosting (temperature monitoring)
Exchanger (plate)
Defrosting
Temperature monitoring defrosting
Pressure monitoring defrosting
Sectional defrosting
Configuration
Calibration
Configuring the DM50-C
Exchanger (liquid)
Changeover
Reversible HP
Fan setpoint compensation
Summer / winter mode
Step controller
Sequential step control
Binary step control
Pretreatment
Cooling recovery mode
Extra controller
External setpoint device
Room controller S-ED-RU-DFO
Preheater
Preheater sub-function: Preheating
Preheater sub-function: Filter drying
Zone control
Zone control: Room cascade configuration example
Fan control
Fan control type
Pressure
Flow
Manual
External
Supply air pressure and extract air fan slave
Supply air pressure with extract air flow slave
Extract air pressure with supply air fan slave
Extract air fan pressure with supply air flow slave
Flow calculation
Fan compensation
Filter monitoring
Guard type filter monitor
Sensor type filter monitor
Filter calibration
Periodic filter replacement
Humidity control
Humidification
Dehumidification (Separate dehumidification unit)
Dehumidification (Sequence override)
Demand control
Air quality control
Fan start/stop
Mixing damper function
Free cooling
Humidification + Dehumidification
Humidity neutral zone
Support control
Enthalpy control
Dampers
Outdoor damper (Open/Closed)
Exhaust (Open/Closed)
EATR control (Modulated)
Recirculation (Open/Closed)
I/O allocation settings
Digital inputs
DI: Cooling/(Heating) changeover
DI: Lock PID controller supply
DI: Filter guard supply air
DI: Filter guard extract air
DI: Feedback fire damper
Digital outputs
Analog outputs
Analog inputs
AI: External setpoint temperature
AI: Pressure filter supply air
AI: Pressure filter extract air
Extra sensors & inputs
Alarm acknowledgment
Extra sensors
Extra alarm
Extra indications & outputs
Extra time channel
Run indication
Sum alarm output
Auxiliary indication
Temperature output
Energy insight
Power usage fans
Power usage heater
Power recovery exchanger
Heat exchanger efficiency monitoring
Fire/Smoke
Fire mode damper
Smoke detector input (T1)
Fail-safe
Starting and stopping the unit
Schedule
Extended running
Digital input
Navipad
Room unit
External stop
Communication
Ports
Int-link
BMS
Ext-link
EFX
Connected devices
Modbus Fan
Modbus Pressure transmitter
Modbus Rotary exchanger
Modbus Damper
Modbus Section defrosting module (DM50-C)
Modbus Heat pump
EXOline Room unit ED-RUx
Modbus Room unit ED-RUD
Setting up the room unit
Modbus Room unit ED-RUD
Device status
BMS watchdog
Alarms
Reviewing alarms
Alarm history
Alarm snapshot
Configuring alarms
Browsing alarms
Air and temperature control
1015 Deviation alarm supply air fan
1020 Deviation alarm extract air fan
1030 Deviation alarm supply temp zone 1
1035 Deviation alarm supply temp zone 2
1040 Deviation alarm supply temp zone 3
1070 Efficiency exchanger
1080 Deviation alarm supply air temperature
1085 Leakage heater valve
Analog inputs
2005 Outdoor temperature
2010 Intake air temperature
2015 Supply air temperature
2020 Exhaust air temperature
2025 Extract air temperature
2030 Room temperature 1
2035 Room temperature 2
2040 Room temperature 3
2045 Room temperature 4
2050 Pressure supply air
2055 Pressure extract air
2060 Flow supply air
2065 Flow extract air
2070 Flow exchanger supply air
2075 Pressure exchanger extract air
2080 Defrosting temperature
2085 Freeze protection temperature 1
2090 Freeze protection temperature 2
2095 Freeze protection temperature 3
2100 CO2 room/extract air
2105 Humidity room/extract air
2110 Humidity supply air
2115 Humidity outdoor
2120 Extra controller temperature
2125 External control supply air fan
2130 External control extract air fan
2135 Extra sensor 1
2140 Extra sensor 2
2145 Extra sensor 3
2150 Extra sensor 4
2155 Extra sensor 5
2160 External setpoint temperature
2165 External setpoint flow
2170 Pressure filter supply air
2175 Pressure filter extract air
2180 Efficiency temperature exchanger
2185 Preheater temperature
2190 Supply air temperature zone 1
2195 Supply air temperature zone 2
2200 Supply air temperature zone 3
2205 Extract air temperature zone 1
2210 Extract air temperature zone 2
2215 Extract air temperature zone 3
2220 Room air temperature zone 1
2225 Room air temperature zone 2
2230 Room air temperature zone 3
2235 Freeze protection temperature zone 1
2240 Freeze protection temperature zone 2
2245 Freeze protection temperature zone 3
2250 Position feedback cooler valve
2255 Position feedback outdoor air damper
2260 Position feedback recirculation damper
2265 Pressure EATR
2270 Pressure pre-filter supply air
2275 Pressure end-filter supply air
2280 Pressure pre-filter extract air
Component malfunction
Extra functions
4030 Deviation alarm humidity control
4035 Deviation alarm extra controller
Extra sensors and alarms
Fire/Smoke
Manual operation and warnings
Dictionary
New keyword
Access Configuration Manual
(latest update:
4/24/2024
)
Access 4.x
Access 5.x
×