Access 5.x |
Alarms > Analog input > 2020 Exhaust air temperature |
Default settings:
Fault (No sensor or signal) |
➔ |
➔ |
Action fault |
|||
Original name |
Exhaust air temperature |
Normal stop |
||||
Low limit |
10 oC |
➔ |
➔ |
Action low limit |
||
Defined by the user |
Alarm No |
2020 |
No action |
|||
Level |
Class B |
|||||
High limit |
30 oC |
➔ |
Delay |
5s |
➔ |
Action high limit |
Defined by the user |
No action |