Access 5.x |
Component malfunction alarms |
ID |
Name |
Alarm trigger |
3005 |
Malfunction Fire Damper |
DI: Feedback fire damper. Fire damper exercise test failed |
3010 |
Malfunction Extra Fan Motor 1 |
DI: Alarm extra fan motor 1 |
3015 |
Malfunction Extra Fan Motor 2 |
DI: Alarm extra fan motor 2 |
3020 |
Malfunction Pump (Seq-A) |
DI: Feedback heating (SEQ-A) |
3025 |
Malfunction Pump (Seq-B) |
DI: Feedback exchanger (SEQ-B) |
3030 |
Malfunction Pump (Seq-C) |
DI: Feedback cooling (SEQ-C) |
3035 |
Malfunction Pump (Seq-D) |
DI: Feedback recirculation 1 (SEQ-D) |
3040 |
Malfunction Pump (Seq-E) |
DI: Feedback recirculation 2 (SEQ-E) |
3045 |
Malfunction Pump (Seq-F) |
DI: Feedback fan setpoint comp (SEQ-F) |
3050 |
Malfunction Pump (Seq-G) |
DI: Feedback heating 2 (SEQ-G) |
3055 |
Malfunction Pump (Seq-H) |
DI: Feedback cooling 2 (SEQ-H) |
3060 |
Malfunction Pump (Seq-I) |
DI: Feedback exchanger extract (SEQ-I) |
3065 |
Malfunction Pump (Seq-J) |
DI: Feedback external heating/cooling (SEQ-J) |
3070 |
Rotary exchanger alarm |
Exchanger rotation guard alarm |
3075 |
Internal battery error |
Internal battery needs replacing |
3080 |
Communication fault device |
Device on the bus is not responding |
3085 |
Malfunction extra controller |
DI: Feedback extra controller |
3090 |
Internal error |
Internal error in the controller |
3095 |
Malfunction preheater |
DI: Feedback preheater |
3100 |
Communication fault BMS master |
Triggered by BMS watchdog in case of communication interupt |
3105 |
Malfunction heating zone 1 |
DI: Feedback heating zone 1 |
3110 |
Malfunction heating zone 2 |
DI: Feedback heating zone 2 |
3115 |
Malfunction heating zone 3 |
DI: Feedback heating zone 3 |
3120 |
Malfunction cooling zone 1 |
DI: Feedback cooling zone 1 |
3125 |
Malfunction cooling zone 2 |
DI: Feedback cooling zone 2 |
3130 |
Malfunction cooling zone 3 |
DI: Feedback cooling zone 3 |
3135 |
Device warning |
Controller is reading (via internal modbus) internal warning of the device |
3140 |
Device alarm |
Controller is reading (via internal modbus) internal alarm of the device |
3145 |
Malfunction SAF |
DI: Feedback supply air fan / Triggered from Modbus fan, if the fan is supposed to run but run indication can't be read out from the fan |
3150 |
Malfunction EAF |
DI: Feedback extract air fan / Triggered from Modbus fan, if the fan is supposed to run but run indication can't be read out from the fan |
3155 |
Heat pump B-alarm |
Feedback signal from the heatpump |
3160 |
Heat pump C-alarm |
Feedback signal from the heatpump |