Access 5.x

Component malfunction alarms


ID

Name

Alarm trigger

3005

Malfunction Fire Damper

DI: Feedback fire damper. Fire damper exercise test failed

3010

Malfunction Extra Fan Motor 1

DI: Alarm extra fan motor 1

3015

Malfunction Extra Fan Motor 2

DI: Alarm extra fan motor 2

3020

Malfunction Pump (Seq-A)

DI: Feedback heating (SEQ-A)

3025

Malfunction Pump (Seq-B)

DI: Feedback exchanger (SEQ-B)

3030

Malfunction Pump (Seq-C)

DI: Feedback cooling (SEQ-C)

3035

Malfunction Pump (Seq-D)

DI: Feedback recirculation 1 (SEQ-D)

3040

Malfunction Pump (Seq-E)

DI: Feedback recirculation 2 (SEQ-E)

3045

Malfunction Pump (Seq-F)

DI: Feedback fan setpoint comp (SEQ-F)

3050

Malfunction Pump (Seq-G)

DI: Feedback heating 2 (SEQ-G)

3055

Malfunction Pump (Seq-H)

DI: Feedback cooling 2 (SEQ-H)

3060

Malfunction Pump (Seq-I)

DI: Feedback exchanger extract (SEQ-I)

3065

Malfunction Pump (Seq-J)

DI: Feedback external heating/cooling (SEQ-J)

3070

Rotary exchanger alarm

Exchanger rotation guard alarm

3075

Internal battery error

Internal battery needs replacing

3080

Communication fault device

Device on the bus is not responding

3085

Malfunction extra controller

DI: Feedback extra controller

3090

Internal error

Internal error in the controller

3095

Malfunction preheater

DI: Feedback preheater

3100

Communication fault BMS master

Triggered by BMS watchdog in case of communication interupt

3105

Malfunction heating zone 1

DI: Feedback heating zone 1

3110

Malfunction heating zone 2

DI: Feedback heating zone 2

3115

Malfunction heating zone 3

DI: Feedback heating zone 3

3120

Malfunction cooling zone 1

DI: Feedback cooling zone 1

3125

Malfunction cooling zone 2

DI: Feedback cooling zone 2

3130

Malfunction cooling zone 3

DI: Feedback cooling zone 3

3135

Device warning

Controller is reading (via internal modbus) internal warning of the device

3140

Device alarm

Controller is reading (via internal modbus) internal alarm of the device

3145

Malfunction SAF

DI: Feedback supply air fan / Triggered from Modbus fan, if the fan is supposed to run but run indication can't be read out from the fan

3150

Malfunction EAF

DI: Feedback extract air fan / Triggered from Modbus fan, if the fan is supposed to run but run indication can't be read out from the fan

3155

Heat pump B-alarm

Feedback signal from the heatpump

3160

Heat pump C-alarm

Feedback signal from the heatpump