Access 4.x

Ports > Ext-link


Configuration of Ext-link port for connection to external modbus components


Variable

Available options & Selection

Note


Configure communication settings

Configuration > System settings > Communication > Communication port: Ext-link

Function

| EXOline slave| EXOline master | Modbus slave | Modbus master| External display | EFX master |

Modbus master - for connection and control of Modbus components

Format

|8N1| 8E1 | 8O1 | 8N2 | 8E2 | 8O2 |

Structure of data packet:

8 - Data bits

N - Parity: None | Even | Odd

1 - Stop bits: 1 | 2

Baud rate

|9600 bps| 14400 bps |…| 115200 bps |

Data exchange speed



Configuration of Ext-link port for connection to EXOline expansion units


Variable

Available options & Selection

Note


Configure communication settings

Configuration > System settings > Communication > Communication port: Ext-link

Function

| EXOlive slave | EXOline master | Modbus slave | Modbus master| External display | EFX master |

EXOline master - for connection to Regin's expansion units (E15, E28, Pressigo EXOline, etc.)

Format

|8N1| 8E1 |8O1| 8N2 | 8E2 | 8O2 |

Structure of data packet:

8 - Data bits

O - Parity: None | Even | Odd

1 - Stop bits: 1 | 2

Baud rate

|9600 bps| 14400 bps |…| 115200 bps |

Data exchange speed