Access 4.x

Ports > Int-link


Configuration of Int-link port for connection to internal modbus components



Variable

Available options & Selection

Note


Configure communication settings

Configuration > System settings > Communication > Communication port: Int-link 1 & 2

Function

| EXOline slave|EXOline master | Modbus slave | Modbus master|External display | EFX master |

Modbus master - for connection and control of Modbus components (fans, exchanges, dampers, etc.)

Format

| 8N1| 8E1 | 8O1 | 8N2 | 8E2 | 8O2 |

Structure of data packet:

8 - Data bits

N - Parity: None | Even | Odd

1 - Stop bits: 1 | 2

Baud rate

| 9600 bps| 14400 bps |…| 115200 bps |

Data exchange speed