Access 4.x

Manual control > Manual control of the Heating/Cooling sequences


Caution: Manual control should exclusively be employed for testing and commissioning activities.


Heating/Cooling sequences can be configured to achieve the desired outputs from connected peripheral devices.


Manual control of sequence output




Variable

Available options & Selection

Note


Manual control of the Sequence output

Data & Settings > In-/Output status > Heating/Cooling sequences

Heating

Position: SEQ-A

Position: SEQ-A - Original name of the sequence


Mode: | Auto | - Output of the sequence regulated by the controller


Mode: | Manual | - Output of the sequence set by the user


Manual: [50.0] % - Output of the sequence if manual control is activated


Actual value: 0.0 % - Actual output of the sequence

 

Mode: | Auto | Manual |

Manual: [0.0] %

Actual value: 0.0 %

Exchanger

Position: SEQ-B

Mode: | Auto | Manual |

Manual: [50.0] %

Actual value: 50.0 %

Cooling

Position: SEQ-C

Mode: | Auto | Manual |

Manual: [40.0] %

Actual value: 0.0 %