Access 4.x

Manual control > Manual control of the Input/Output


Caution: Manual control should exclusively be employed for testing and commissioning activities.


Inputs can be manually set to replicate the required values of connected sensors, transmitters, or switches.

Outputs can be manually activated to control components, indicators (DO), and adjust speed or capacity (AO).


Manual control of the Inputs and Outputs


Variable

Available options & Selection

Note


Manual control of the Analog inputs

Data & Settings > In-/Output status > Analog inputs

Mode: | Auto | - Measuring input of the controller


Mode: | Manual | - Input set by the user

Manual: [18.0] oC - Input value if manual control is activated


Actual value: 18.0 oC - Actual input value the application operates with

Supply temperature

Mode: | Auto | Manual |

Manual: [18.0] oC

Actual value: 18.0 oC


Manual control of the Digital inputs

Data & Settings > In-/Output status > Digital inputs

Mode: | Auto | - Measuring input of the controller


Mode: | Off | On | - Input set by the user


Actual value: Off / On - Actual input value the application operates with

External stop

Mode: | Off | On | Auto |

Actual value: Off | On


Manual control of the Analog outputs

Data & Settings > In-/Output status > Analog outputs

Mode: | Auto | - Output regulated by the controller


Mode: | Manual | - Output set by the user

Manual: [50.0] % - Output value if manual control is activated


Actual value: [50.0] % - Actual output

Humidity control

Mode: | Auto | Manual |

Manual: [50] %

Actual value: 50 %


Manual control of the Digital outputs

Data & Settings > In-/Output status > Digital outputs

Mode: | Auto | - Application sets the output of the controller


Mode: | Off | On | - Output set by the user


Actual value: Off / On - Actual output state

Running indication

Mode: | Off | On | Auto |

Actual value: Off | On