Access 5.x |
Alarms > Component malfunction > 3170 Gas detection alarm |
Refrigerant gas has been detected. Gas evacuation mode is active for 2 hours after the gas level has fallen below the alarm limit.
The gas detection alarm can only be acknowledged through a dedicated digital input. Before the alarm can be cleared, the AHU must be physically inspected to verify safe operating conditions.The reset push-button must then be pressed and held for a minimum of 5 seconds to activate the digital input and reset the alarm.
Default settings:
➔ |
|||
Refrigerant gas detector |
Action |
Normal Speed |
|
Level |
Class A |
||
Delay |
5 s |
||
Alarm No |
3170 |
||
Name |
Gas detection alarm |
||
Original name |
Gas detection alarm |
||
Related topics: