Access 4.x |
Changeover configuration example |
Changeover is a separate unit providing both heating and cooling on demand. The changeover is a standalone unit with separate controller present. The demand for heating or cooling is switched and regulated from the hardwired Access controller.
The table below shows a configuration example of the changeover unit.
Variable |
Available options & Selection |
Note |
|
Sequence selection |
|||
Configuration > Functions > Function activation > Heating/Cooling sequence setup |
|||
Sequence for heating |
|...| SEQ-G Heating 2 | SEQ-H |...| |
||
Sequence for cooling |
|...| SEQ-G | SEQ-H Cooling 2 |...| |
||
Sequence settings |
|||
Configuration > Functions > Function activation > Heating/Cooling sequence setup > Heating 2 |
|||
Type of sequence |
|...| Heating |...| |
||
Type of heater |
| Water | Electric| DX | Combi coil | |
||
Type of feedback |
| None | Alarm | Run indication | |
||
Digital start output |
| No | Yes | |
||
Sequence output when recirculation/support |
| 0% | 100% | Auto | |
||
Sequence output min limit |
0% |
||
Sequence output max limit |
100% |
||
Sequence output when the unit is stopped |
0% |
||
Configuration > Functions > Function activation > Heating/Cooling sequence setup > Cooling 2 |
|||
Type of sequence |
|Cooling |...| |
||
Type of cooler |
| Water | DX | DX with exchanger control | |
||
Type of feedback |
| None | Alarm | Run indication | |
||
Digital start output |
| No | Yes | |
||
Sequence output when recirculation/support |
| 0% | 100% | Auto | |
||
Sequence output min limit |
0% |
||
Sequence output max limit |
100% |
||
Sequence output when the unit is stopped |
0% |
||
Changeover settings |
|||
Configuration > Functions > Function activation > Heating/Cooling sequence setup > Changeover settings |
|||
Changeover 1 |
|||
Changeover sequence for heating |
… | Disabled | … |
||
Changeover sequence for cooling |
… | Disabled | … |
||
Changeover 2 |
|||
Changeover sequence for heating |
… | Heating 2 | … |
||
Changeover sequence for cooling |
… | Cooling 2 | … |
||
PID Settings |
|||
Configuration > PID controllers > Heating 2 |
|||
P-band |
10 oC |
||
I-time |
100 s |
||
D-time |
0 s |
||
Configuration > PID controllers > Cooling 2 |
|||
P-band |
10 oC |
||
I-time |
100 s |
||
D-time |
0 s |
||
Hardwired interface to the pump & valve |
|||
Configuration > I/O allocation settings > |
|||
Digital inputs > Feedback Heating 2 (SEQ-G) |
Any available I/O |
||
Digital inputs > Feedback cooling 2 (SEQ-H) |
|||
Digital inputs > Cooling/(Heating) changeover 2 |
|||
Digital inputs > Lock PID controller supply |
|||
Digital outputs > Cooling 2 start (SEQ-H) |
|||
Digital outputs > Changeover 2 |
|||
Analog outputs > Changeover 2 |
|||
Heater starting and stopping |
|||
Data & Settings > Temperature control > Heating 2 |
|||
Digital start output start point |
10% |
Output of the supply controller to start and stop the heater |
|
Digital start output stop point |
1% |
||
Cooling control settings |
|||
Data & Settings > Temperature control > Cooling 2 |
|||
Digital start output start point |
10% |
Output of the supply controller to start and stop the DX cooler |
|
Digital start output stop point |
1% |
||
Block DX-cooling if outdoor temperature < |
0 oC |
||
Block DX-cooling if supply air fan output signal < |
0% |
||
Hysteresis if outdoor temperature block |
1 oC |
||
Reduction of min limit supply air if active DX-cooling |
5 oC |
||
Graphical representation |
|||
Flowchart |
|||
58 % - indicates the output of either Heating 2 sequence or Cooling 2 sequence (depending if there is a demand for heating or cooling) |
Chapter info
Last reviewed: 06/21/2022
Access version: 4.6-1-02 (3354)