Access 5.x |
Configuration wizard |
The configuration wizard is a menu that simplify the procedure to Activate and Configure common accessories and functions and Allocate it’s in- and outputs.
The wizard makes necessary configurations automatically and guide the user through limited options.
Access the configuration wizard via in the navigation bar or via the configuration menu.
Note: The wizard’s availability and content depend on the air handling unit’s model and controller software version.
If the configuration wizard does not cover the desired accessory or function it can still be configured via the configuration menu.
Set up an accessory or function with the configuration wizard
Activation (Configuration > Configuration wizard) Select the type of accessory or function you wish to set up. E.g. if you have installed a water coil for cooling as accessory, select Set up cooler. |
||||
Configuration > Configuration wizard |
24 Jun 10:31 |
|||
Set up pressure control |
> |
|||
Set up cooler |
> |
|||
Set up changeover |
> |
|||
Exit to configuration menu > |
Complete configuration wizard > |
|||
Configuration (Configuration > Configuration wizard > Set up “function”) Specify the details of the accessory or function you wish to set up. E.g. If the cooler you wish to set up is of type Water and that the circulation pump is with an alarm feedback signal. |
||||
Configuration > Configuration wizard > Set up cooler |
24 Jun 10:31 |
|||
Type of cooler |
Water |
|||
Type of feedback |
Alarm |
|||
Pump control |
Yes |
|||
Pump running mode |
Auto |
|||
Confirm configuration and continue > |
||||
Allocation (Configuration > Configuration wizard > Set up “function” > In-/Outputs) Confirm the in-/output allocation of the connected signals and sensors. Configure in-/output settings (sensor measuring range, polarity, edit name of sensor/signal etc.) as necessary. Complete the setup by pressing Confirm In-/Outputs and complete setup. |
||||
Configuration > ... > Set cooler > In-/Outputs |
24 Jun 10:31 |
|||
Analog outputs |
Range output |
Device |
Position |
|
Cooling (SEQ-C) |
0–10V |
Controller |
AO2 |
|
Digital outputs |
Contact function |
Device |
Position |
|
Cooling pump (SEQ-C) |
Normally open |
Controller |
DO3 |
|
Digital Inputs |
Contact function |
Device |
Position |
|
Feedback cooling (SEQ-C) |
Normally open |
Controller |
DI5 |
|
Confirm In-/Outputs and complete setup > |
||||
Completing the configuration wizard A completed setup is listed as Configured in the configuration wizard menu. To make changes to an already configured function, rerun the wizard or use the configuration menus. |
||||
Configuration > Configuration wizard |
24 Jun 10:31 |
|||
Set up pressure control |
> |
|||
Set up cooler |
Configured |
> |
||
Set up changeover |
> |
|||
Exit to configuration menu > |
Complete configuration wizard > |
|||
Operation setting Functions configured via the wizard still require adaptation of its operation settings (limits, setpoint). Navigate to relevant category, choose function and adjust the values if needed. |
||||
Data & Settings |
24 Jun 10:31 |
|||
Temperature control |
> |
|||
Fan control |
> |
|||
Demand control |
> |
|||
Note: When the installation is complete and all functions are tested it is recommended to save a local backup of the current configuration in the control unit.
Select Yes on Save commissioning settings in the Configuration > System settings > Save and restore settings menu