Access 4.x |
Extra controller |
An independent temperature controller for regulating of additional heater or cooler. The controller has an analog input signal for temperature sensors and an analog output signal 0 to 10 V. There is also a digital output signal which is activated when the analog output signal is above 10% (1 V) and deactivated when the analog signal is below 1% (0.1 V).
The controller is configured to be active all the time, follow operation of the unit, run only during defrosting or follow the scheduler.
An alarm will be triggered if Extra controller is in manual override or if a sensor error occurs. The extra controller can also be enhanced with the frost protection if a water based heater is used.
Overview of the menu choices for configuring and settings of the extra controller |
||
Variable |
Available options & Selection |
|
Activate extra controller |
||
Configuration > Functions > Function activation |
||
Extra controller |
| Yes | No | |
|
Configuration settings |
||
Configuration > Functions > Extra controller |
||
Start/Stop function |
| Always running | Unit running | When defrosting | | Extra time channel 1 | Extra time channel 2 | | Extra time channel 3 | |
|
Control mode |
| Heating | Cooling | |
|
Type of freeze protection |
| Select | Freeze protection temperature 1 | | Freeze protection temperature 2 | | Freeze protection temperature 3 | |
|
Pump control |
| No | Yes | |
|
Pump running mode |
| Always running | Auto | |
|
Type of feedback |
| None | Alarm | Run indication | |
|
Digital start output |
| None | Yes | |
|
Extra contr. Output when recirculation/support |
| 0% | 100% | Auto | |
|
Extra contr. Output min limit |
[0] % |
|
Extra contr. Output max limit |
[100] % |
|
PID Settings |
||
Configuration > PID controllers > Extra controller |
||
P-band |
[33] oC |
|
I-time |
[100] s |
|
D-time |
[0] s |
|
Hardwired interface to the sensor, heater/cooler |
||
Configuration > I/O allocation settings > |
||
Analog inputs > Extra controller temperature |
Any available I/O |
|
Digital inputs > Feedback extra controller |
||
Digital outputs > Extra controller start |
||
Digital outputs > Extra controller pump |
||
Analog outputs > Extra controller |
||
Operational settings |
||
Data & Settings > Temperature control > Extra controller |
||
Setpoint extra controller |
[18] oC |
|
Digital start output start point |
[10] oC |
|
Digital start output start point |
[1] % |
|
Pump stop delay |
[5] min |
|
Pump-kick hour |
[15] h |
|
Pump running when outdoor temperature < |
[10] oC |
|
Hysteresis to allow pump stop |
[1] oC |
|
Freeze protection > |
||
Setpoint |
||
Data & Settings > Operation overview > Temperature |
||
Setpoint extra controller |
[18] oC |
|
Temperature extra controller |
__ oC |
|
Alarm settings |
||
Configuration > Alarms > Extra functions |
||
Extra functions > Malfunction extra controller (181) |
||
Manual operation and warnings > Manual operation extra controller (141) |