Access 5.x

Guard type filter monitor


Filter guard utilizes pressure switches set for the specific pressure difference over the filter.


Configuration and settings for guard type filter monitoring



Variable

Available options & Selection

Note


Activate filter monitoring function

Configuration > Functions > Function activation

Filter monitoring

| Yes | No |



Configuration of filter monitoring function

Configuration > Functions > Filter monitoring

Supply air pre-filter

| No | Sensor | Guard |

Enable filters by selecting filter monitor type

Supply air filter

| No | Sensor | Guard |

Supply air end-filter

| No | Sensor | Guard |

Extract air pre-filter

| No | Sensor | Guard |

Extract air filter

| No | Sensor | Guard |

Filter classification setup

>

Filter calibration related settings

Reset sevice interval times

| Yes | No |

Periodic service related settings

Service interval

[0] months


Configure inputs

Configuration > I/O allocation settings > Digital inputs >

Pre-filter guard supply air

Any available I/O

Configure digital inputs the pressure switches are connected to

Filter guard supply air

End-filter guard supply air

Pre-filter guard extract air

Filter guard extract air


Filter alarms

Configuration > Alarms > Air and temperature control >

1090 Pre-filter guard supply air

>

Adjust alarm settings if necessary

1000 Filter guard supply air

>

1095 End filter guard supply air

>

1100 Pre-filter guard extract air

>

1005 Filter guard extract air

>