Access 5.x |
Modbus connected damper actuator |
Example of setting connection to Modbus damper actuators |
|||
Variable |
Available options & Selection |
Note |
|
Configuration of Modbus connected actuators |
|||
Configuration > System settings > Communication Devices > Device 11 |
|||
Type |
...| Damper (Modbus) |... |
Select type of the connected device (Damper) |
|
Brand |
| Belimo | |
Select brand of the damper actuator |
|
Address |
[0] > [21] |
Enter the same address as is configured in the damper actuator |
|
Function |
...| Outdoor air damper | Exhaust air damper |... |
Assign function (Select damper the actuator is mounted to) |
|
Name |
[Device 11] > [Fresh air damper] |
Change default name to a more informative |
|
Communication type |
| RTU | TCP | |
- |
|
Communication port |
| Ext-link | BMS | Int-link 1 & 2 | |
Select port for communication to the device |
|
Configuration > System settings > Communication Devices > Device 12 |
|||
Type |
...| Damper (Modbus) |... |
Select type of the connected device (Damper) |
|
Brand |
| Belimo | |
Select brand of the damper actuator |
|
Address |
[0] > [22] |
Enter the same address as is configured in the damper actuator |
|
Function |
...| Outdoor air damper | Exhaust air damper |... |
Assign function (Select damper the actuator is mounted to) |
|
Name |
[Device 12] > [Exhaust air damper] |
Change default name to a more informative |
|
Communication type |
| RTU | TCP | |
- |
|
Communication port |
| Ext-link | BMS | Int-link 1 & 2 | |
Select port for communication to the device |
Tip: Check device status after configuration