Access 5.x |
Modbus connected sectional defrosting module |
Example of setting connection to DM50-C module |
|||
Variable |
Available options & Selection |
Note |
|
Modbus connection to DM50-C module |
|||
Configuration > System settings > Communication Devices > Device 7 |
|||
Type |
...| Section defrosting (Modbus) | … |
Select type of the connected device (Sectional defrosting) |
|
Brand |
| DM50-C | |
Select DM50-C |
|
Address |
[0] > [53] |
Enter the same address as is configured in the DM50-C (default address is 53) |
|
Name |
[Device 7] > [Defrosting module] |
Change default name to a more informative |
|
Communication type |
| RTU | TCP | |
- |
|
Communication port |
| Ext-link | BMS | Int-link 1 & 2 | |
Select port for communication to the device |
|
Activation of modbus in the DM50-C module |
|||
Configuration > Functions > Temperature control > Sectional defrosting > DM50-C configuration |
|||
Activate Modbus control |
| No | Yes | |
Activate Modbus control |
Tip: Check device status after configuration