Modbus connected fan |
Example of setting connection to Modbus connected fans |
|||
Variable |
Available options & Selection |
Note |
|
Configuration of Modbus connected fans |
|||
Configuration > System settings > Communication Devices > Device 1 |
|||
Type |
| Disabled | Fan (Modbus) | … |
Select type of the connected device (Fan) |
|
Brand |
…| EBM-PAPST |… |
Select brand of the fan |
|
Address |
[0] > [1] |
Enter the same address as configured in the fan |
|
Function |
| Select | Supply air fan | Extract air fan | |
Assign function (Supply air fan) |
|
Name |
[Device 1] > [SAF1] |
Change default name to a more informative |
|
Communication type |
| RTU | TCP | |
- |
|
Communication port |
| Ext-link | BMS | Int-link 1 & 2 | |
Select port for communication to the device |
|
Configuration > System settings > Communication Devices > Device 2 |
|||
Type |
| Disabled | Fan (Modbus) | … |
Select type of the connected device (Fan) |
|
Brand |
…| EBM-PAPST |… |
Select brand of the fan |
|
Address |
[0] > [2] |
Enter the same address as is configured in the fan |
|
Function |
| Select | Supply air fan | Extract air fan | |
Assign function (Extract air fan) |
|
Name |
[Device 2] > [EAF1] |
Change default name to a more informative |
|
Communication type |
| RTU | TCP | |
- |
|
Communication port |
| Ext-link | BMS | Int-link 1 & 2 | |
Select port for communication to the device |
Tip: Check device status after configuration