Access 5.3 and later |
Modbus connected Refrigerant detector |
Example of setting connection to the Refrigerant gas leakage detection sensor |
|||
Variable |
Available options & Selection |
Note |
|
Configuration of Modbus connected gas sensor |
|||
Configuration > System settings > Communication Devices > Device 29 |
|||
Type |
| Disabled | ... | Refrigerant detector | |
Select type of the connected device |
|
Brand |
| Select | Senseair R454B | |
Select type of the sensor |
|
Address |
[0] > [104] |
Enter the default address of the sensor (104) |
|
Function |
| Gas sensor 1 SA | Gas sensor 1 EA | | Gas sensor 2 SA | Gas sensor 2 EA | |
Assign function (Location and number of the installed sensor) |
|
Name |
[Device 29] > [Gas sensor 1 SA] |
Change default name to more informative |
|
Communication type |
| RTU | TCP | |
- |
|
Communication port |
| Ext-link | BMS | Int-link 1 & 2 | |
Select port for communication to the device |
|
Status |
Disconnected / Connected / Device internal Error |
||
Gas detection sensor Modbus address setup → |
Changing of the default modbus address of the sensor |
||
Gas detection sensor Modbus address setup → |
|||
Variable |
Available options & Selection |
Note |
|
Changing address of the gas sensor |
|||
Configuration > System settings > Communication Devices > Device 29 > Sensor setup |
|||
Address |
[104] |
Enter address of the sensor (default address:104) |
|
Status |
|
Make sure the connection is established (status icon is green) |
|
New address |
[201] |
Enter the new address for the sensor |
|
|
Press the "Set new address" button |
||
Tip: Check device status after configuration