Access 5.x |
Modbus connected refrigerant detector |
Example of setting up refrigerant detector |
|||
Variable |
Available options & Selection |
Note |
|
Configuration of Modbus connected refrigerant detector |
|||
Configuration > System settings > Communication Devices > Device 21 |
|||
Type |
| Disabled | ... | Refrigerant detector | |
Select type of the connected device |
|
Brand |
| Select | Senseair RDS | |
Select brand |
|
Address |
[0] > [111] |
Enter the same address as configured in the detector |
|
Function |
| Select | | Gas sensor 1 SA | | Gas sensor 1 EA | | Gas sensor 2 SA | | Gas sensor 2 EA | |
Assign function (Spare expansion unit number) |
|
Name |
[Device 21] > [Gas sensor SA 1] |
Change default name to more informative |
|
Communication type |
| RTU | TCP | |
- |
|
Communication port |
| Ext-link | BMS | Int-link 1 & 2 | |
Select port for communication to the device |
|
Status |
|
Disconnected |
|
|
Connected |
||
Gas detection sensor Modbus address setup → |
See the configuration example bellow |
||
Establishing connection to and changing address of the refrigerant detector |
|||
Variable |
Available options & Selection |
Note |
|
Gas detection sensor Modbus address setup |
|||
Configuration > System settings > Communication Devices > Device 21 > Gas detection sensor Modbus address setup → |
|||
Suppliers default Modbus address |
[104] |
Enter current address of the sensor (default address of the brand new sensor is 104) |
|
Status |
|
RED indicates that connection to the sensor on the above address could not be established. Check settings of the Communication port and type |
|
|
GREEN indicates that the connection has been established.The following new address line and set button have been enabled |
||
New address |
[104] > [111] |
Enter the new modbus address to be stored to the sensor's memory |
|
|
Hit the button to proceed with the change |
||
Related topics:
Heat pump
Senseair RDS (External link)