Modbus connected Heat pump module |
Example of setting connection to the Heat pump control module |
|||
Variable |
Available options & Selection |
Note |
|
Configuration of Modbus connected Heat pump |
|||
Configuration > System settings > Communication Devices > Device 20 |
|||
Type |
| Disabled | ... | Heat pump (Modbus) | |
Select type of the connected device (Heat pump) |
|
Brand |
| 1 Circuit | 1 Circuit with Boost heater | | 2 Circuit | 2 Circuit with Boost heater | |
Select type of the Heat pump |
|
Address |
[0] > [54] |
Enter the same address as configured in the Heat pump |
|
Function |
| Select | Exp1 | Exp2 | Exp3 |... |
Assign function (Spare expansion unit number) |
|
Heat pump sequence |
| Disabled | | Changeover 1 | | Changeover 2 | |
Select the changeover sequence to be related to the operation of the heat pump |
|
Name |
[Device 20] > [Heat pump] |
Change default name to more informative |
|
Communication type |
| RTU | TCP | |
- |
|
Communication port |
| Ext-link | BMS | Int-link 1 & 2 | |
Select port for communication to the device |
Tip: Check device status after configuration