Access 4.x |
Rotary exchanger defrosting (temperature monitoring) |
Exhaust air (alternatively Defrosting) temperature is constantly measured.
The defrosting controller (PID) will take over control of sequence output (reduces rotation speed) if temperature falls below [-3] oC.
The temporary reduction of the exchanger's efficiency has a defrosting effect. The operation returns to normal once temperature and minimal defrosting time conditions are met.
The defrosting can also be triggered via digital input signal. In that case the defrosting is active while digital output signal is present.
It is also possible to combine both options: the defrosting will be active until at least one defrosting start condition is present.
Configuration of defrosting with temperature monitoring |
|||
Variable |
Available options & Selection |
Note |
|
Sequence selection |
|||
Configuration > Functions > Function activation > Heating/Cooling sequence setup |
|||
Sequence for exchanger |
...| SEQ-B Exchanger |... |
Select sequence for exchanger |
|
Sequence settings |
|||
Configuration > Functions > Function activation > Heating/Cooling sequence setup > Exchanger |
|||
Type of sequence |
...| Exchanger |... |
||
Type of exchanger |
| Rotary | Plate | Liquid | |
||
Type of defrosting |
| None | Temperature monitoring | |
||
Defrosting configuration |
|||
Configuration > Functions > Temperature control > Defrosting temperature monitoring |
|||
Temperature sensor |
| Exhaust air | Defrosting | |
||
Extract air fan speed when fan stop defrosting |
|Auto | Low | Normal | High | |
Operation level of the extract air fan when the supply air fan is stopped |
|
Allocate analog input |
|||
Configuration > I/O allocation settings > Analog inputs |
|||
Exhaust air temperature |
Any available I/O |
||
Allocate digital input |
|||
Configuration > I/O allocation settings > Digital inputs |
|||
Defrosting guard exchanger |
Any available I/O |
||
PID Settings |
|||
Configuration > PID controllers > Defrosting |
|||
P-band |
[16] oC |
PID settings for the defrosting controller |
|
I-time |
[240] s |
||
D-time |
[0] s |
||
Defrost operational settings |
|||
Data & Settings > Temperature control > Exchanger > Defrosting temperature monitoring |
|||
Setpoint min limit |
[-3] oC |
Defrosting starts when the exhaust (defrosting) temperature is < -3 oC and will continue until it becomes +1 oC (-3 oC + 4 oC), but not less than 15 minutes |
|
Hysteresis to end defrosting |
[4] oC |
||
Min time |
[15] min |
||
Min output during defrosting |
[40] % |
Rotation of the exchanger will gradually slow down (PID regulated) but not less than minimal output limit |
|
Stop supply air fan if outdoor temp < |
[-100] oC |