up to and including Access 4.5 |
Sensor type filter monitor |
The sensor type filter monitor can only properly function if the air flow of the fan is measured (Flow as fan control type or flow presentation has been activated).
Configuration and settings for sensor type filter monitoring |
|||
Variable |
Available options & Selection |
Note |
|
Activate filter monitoring function |
|||
Configuration > Functions > Function activation |
|||
Filter monitoring |
| Yes | No | |
||
Configuration of filter monitoring function |
|||
Configuration > Functions > Filter monitoring |
|||
Type |
| Sensor | Guard | | Sensor + Guard | |
||
Filter placement |
| Supply air | Extract air | | Supply air + Extract air | |
||
Configure inputs |
|||
Configuration > I/O allocation settings > Analog inputs |
|||
Pressure filter supply air |
Any available I/O |
||
Pressure filter extract air |
|||
Set alarm level |
|||
Configuration > Alarms > Air and temperature control > Filter alarm supply air (53) |
|||
Action |
| No action | ... |
Adjust alarm settings if necessary |
|
Level |
| Class A | Class B | | Class C | | Disabled | |
||
Delay |
[180] s |
Alarm is triggered if excessive pressure drop is present longer than 180s |
|
Limit X1 |
[0] m3/h |
Lower point of pressure drop / airflow dependency |
|
Limit Y1 |
[10] Pa |
||
Limit X2 |
[2000] m3/h |
Higher point of pressure drop / airflow dependency |
|
Limit Y2 |
[150] Pa |
||
Name |
[Filter alarm supply air] |
Customization of the alarm name |
|
Configuration > Alarms > Air and temperature control > Filter alarm extract air (54) |
|||
Action |
| No action | ... |
Adjust alarm settings if necessary |
|
Level |
| Class A | Class B | | Class C | Disabled | |
||
Delay |
[180] s |
Alarm is triggered if excessive pressure drop is present longer than 180s |
|
Limit X1 |
[0] m3/h |
Lower point of pressure drop / airflow dependency |
|
Limit Y1 |
[10] Pa |
||
Limit X2 |
[2000] m3/h |
Higher point of pressure drop / airflow dependency |
|
Limit Y2 |
[150] Pa |
||
Name |
[Filter alarm extract air] |
Customization of the alarm name |