Access 5.x |
Plate exchanger defrosting with temperature monitoring |
Exhaust air (alternatively Defrosting) temperature is constantly measured.
The defrosting controller (PID) will take over control of sequence output (exchanger bypass) if temperature falls below [-3] oC.
The flow of cold Outdoor - Supply air is gradually diverted from the exchanger to bypass while the flow of warm Extract - Exhaust air remains unchanged.
The intended imbalance of the air flows through the exchanger reduces transfer of thermal energy and as a result has a defrosting effect.
Configuration of defrosting with temperature monitoring |
|||
Variable |
Available options & Selection |
Note |
|
Sequence selection |
|||
Configuration > Functions > Function activation > Heating/Cooling sequence setup |
|||
Sequence for exchanger |
...| SEQ-B Exchanger |... |
Select sequence for exchanger |
|
Sequence settings |
|||
Configuration > Functions > Function activation > Heating/Cooling sequence setup > Exchanger |
|||
Type of sequence |
...| Exchanger |... |
||
Type of exchanger |
| Rotary | Plate | Liquid | |
||
Type of defrosting |
...| Temperature monitoring |... |
||
Defrosting configuration |
|||
Configuration > Functions > Temperature control > Defrosting temperature monitoring |
|||
Temperature sensor |
| Exhaust air | Defrosting | |
||
Extract air fan speed when fan stop defrosting |
|Auto | Low | Normal | High | |
Operation level of the extract air fan when the supply air fan is stopped |
|
Allocate analog input |
|||
Configuration > I/O allocation settings > Analog inputs |
|||
Exhaust air temperature |
Any available I/O |
||
PID Settings |
|||
Configuration > PID controllers > Defrosting |
|||
P-band |
[16] oC |
PID settings for the defrosting controller |
|
I-time |
[240] s |
||
D-time |
[0] s |
||
Defrost operational settings |
|||
Data & Settings > Temperature control > Exchanger > Defrosting temperature monitoring |
|||
Setpoint min limit |
[-3] oC |
Defrosting starts when the exhaust (defrosting) temperature is < -3 oC and will continue until it becomes +1 oC (-3 oC + 4 oC), but not less than 15 minutes |
|
Hysteresis to end defrosting |
[4] oC |
||
Min time |
[15] min |
||
Stop supply air fan if outdoor temp < |
[-100] oC |