Air and temperature control related alarms |
Configuration > Alarms > Air and temperature control
ID |
Alarm name |
Alarm trigger |
53 |
Filter alarm supply air (Filter guard supply air) |
DI: Filter guard supply air / filter pressure drop is above the limit at actual airflow. |
54 |
Filter alarm extract air (Filter guard extract air) |
DI: Filter guard extract air / filter pressure drop is above the limit at actual airflow. |
55 |
Alarm low air flow |
DI: Flow guard |
56 |
Extra freeze protection (Freeze protection guard) |
External frost protection thermostat activated |
57 |
Defrost protection exchanger alarm (Defrosting guard exchanger) |
Exchanger deicing pressure switch activated |
63 |
Electric heater is overheated (Overheated electric heater) |
DI: Overheated electric heater |
65 |
Low efficiency exchanger |
Efficiency below limit |
66 |
Defrosting alarm |
Exchanger deicing activated by deicing sensor |
81 |
Deviation Alarm Supply Air Temperature |
Temperature of the supply air is of limit longer than expected |
82 |
Deviation alarm Flow/pressure supply air |
Pressure or airflow of the supply air fan is of limit longer than expected |
83 |
Deviation alarm Flow/pressure extract air |
Pressure or airflow of the extract air fan is of limit longer than expected |
86 |
High supply air temperature |
Temperature above alarm limit |
87 |
Low supply air temperature |
Temperature below alarm limit |
88 |
Supply air temperature max limit |
Temperature above alarm limit |
89 |
Supply air temperature min limit |
Temperature below alarm limit |
90 |
High room temperature |
Temperature above alarm limit |
91 |
Low room temperature |
Temperature below alarm limit |
92 |
High extract air temperature |
Temperature above alarm limit |
93 |
Low extract air temperature |
Temperature below alarm limit |
94 |
High outdoor air temperature |
Temperature above alarm limit |
95 |
Low outdoor air temperature |
Temperature below alarm limit |
96 |
Freeze protection alarm 1 |
Temperature below alarm limit (description of the function) |
97 |
Freeze protection alarm 2 |
Temperature below alarm limit (description of the function) |
98 |
Freeze protection alarm 3 |
Temperature below alarm limit (description of the function) |
187 |
Leakage heater valve |
Delta-t of heater inlet/outlet is higher then preset limit |
213 |
Deviation alarm supply temp zone 1 |
Temperature above/below alarm limit longer than expected |
214 |
Deviation alarm supply temp zone 2 |
Temperature above/below alarm limit longer than expected |
215 |
Deviation alarm supply temp zone 3 |
Temperature above/below alarm limit longer than expected |
216 |
Freeze protection alarm zone 1 |
Temperature below alarm limit. Risk of freezing (description of the function) |
217 |
Freeze protection alarm zone 2 |
Temperature below alarm limit. Risk of freezing (description of the function) |
218 |
Freeze protection alarm zone 3 |
Temperature below alarm limit. Risk of freezing (description of the function) |
219 |
Electric heater is overheated zone 1 |
DI: Overheated electric heater zone 1 |
220 |
Electric heater is overheated zone 2 |
DI: Overheated electric heater zone 2 |
221 |
Electric heater is overheated zone 3 |
DI: Overheated electric heater zone 3 |