Access 4.x |
Extra function related alarms |
Configuration > Alarms > Extra functions
ID |
Alarm name |
Alarm trigger |
33 |
External fan 1 run |
fan is running (run indication) but it is not started by the application |
34 |
External fan 2 run |
fan is running (run indication) but it is not started by the application |
40 |
Malfunction external fan 1 |
DI: Alarm extra fan motor 1 |
41 |
Malfunction external fan 2 |
DI: Alarm extra fan motor 2 |
60 |
External stop |
DI: External stop |
61 |
External alarm |
DI: External alarm activated |
79 |
Alarm service interval |
Periodic filter change reminder |
84 |
Deviation alarm humidity |
Humidity is of limit longer than expected |
85 |
Deviation alarm extra controller |
Temperature of the extra controller is of limit longer than expected |
109 |
High temperature selected sensor 1 |
Temperature above alarm limit |
110 |
Low temperature selected sensor 1 |
Temperature below alarm limit |
111 |
High temperature selected sensor 2 |
Temperature above alarm limit |
112 |
Low temperature selected sensor 2 |
Temperature below alarm limit |
163 |
Sensor error CO2 |
Sensor faulty (Invalid reading) or missing |
164 |
Sensor error humidity room/extract air |
Sensor faulty (Invalid reading) or missing |
165 |
Sensor error humidity supply air |
Sensor faulty (Invalid reading) or missing |
166 |
Sensor error humidity outdoor |
Sensor faulty (Invalid reading) or missing |
167 |
Sensor error extra controller |
Sensor faulty (Invalid reading) or missing |
181 |
Malfunction extra controller |
DI: Feedback extra controller |