Access 4.x

Extra function related alarms


Configuration > Alarms > Extra functions


ID

Alarm name

Alarm trigger

33

External fan 1 run

fan is running (run indication) but it is not started by the application

34

External fan 2 run

fan is running (run indication) but it is not started by the application

40

Malfunction external fan 1

DI: Alarm extra fan motor 1

41

Malfunction external fan 2

DI: Alarm extra fan motor 2

60

External stop

DI: External stop

61

External alarm

DI: External alarm activated

79

Alarm service interval

Periodic filter change reminder

84

Deviation alarm humidity

Humidity is of limit longer than expected

85

Deviation alarm extra controller

Temperature of the extra controller is of limit longer than expected

109

High temperature selected sensor 1

Temperature above alarm limit

110

Low temperature selected sensor 1

Temperature below alarm limit

111

High temperature selected sensor 2

Temperature above alarm limit

112

Low temperature selected sensor 2

Temperature below alarm limit

163

Sensor error CO2

Sensor faulty (Invalid reading) or missing

164

Sensor error humidity room/extract air

Sensor faulty (Invalid reading) or missing

165

Sensor error humidity supply air

Sensor faulty (Invalid reading) or missing

166

Sensor error humidity outdoor

Sensor faulty (Invalid reading) or missing

167

Sensor error extra controller

Sensor faulty (Invalid reading) or missing

181

Malfunction extra controller

DI: Feedback extra controller