Access 5.x

Analog inputs


All analogue inputs are for PT1000 or 0…10 V.

Input signals can be compensated e.g. for wiring resistance.


If inputs have been assigned to pressure or flow control of fans, alternatively humidity or CO2 control,

the corresponding units will be shown next to the value.


Set the parameter values that should correspond to the input signal levels 0 V and 10 V.


The filter factor is the damping you want the program to work with in order to reduce the influence

of potential signal fluctuations on the sensor input.


A new value is calculated using the following formula:


New value = old value * filter factor + raw value * (1 - filter factor)




Allocate physical analog inputs

Configuration > I/O allocation settings > Analog inputs

Analog inputs

Device

Position

Outdoor temperature

Controller

AI4

Supply air  temperature

SA DPT (Exp 1)

UI1

Room temperature

Device 25

Temperature

Extra sensor 1

Controller

Select I/O

...



Click on the name or  to enter settings. Adjust the name and change the default state of the input if necessary.

Select device used for this function. It can be either the Controller itself or one of the expansion modules.

Select the actual physical input used for this function.





Variable

Available options & Selection

Note


Rename and change the default state if necessary

Configuration > I/O allocation settings > Analog inputs > Extra sensor 1

Name

[Extra sensor 1] > [Reception Temp]

Changeable name

Original name

Extra sensor

Unchangeable name

Sensor type

| Temperature |

| Pressure |

| Control signal |

| Humidity |

| CO2 |

| Pressure for flow calculation |

| Flow |

-

Signal type

| PT1000 | 0-10V |

-

Filter factor

[ 0.2 ]

-

Correction

[ 0.0 ]

-