All analogue inputs are for PT1000 or 0…10 V.
Input signals can be compensated e.g. for wiring resistance.
If inputs have been assigned to pressure or flow control of fans, alternatively humidity or CO2 control,
the corresponding units will be shown next to the value.
Set the parameter values that should correspond to the input signal levels 0 V and 10 V.
The filter factor is the damping you want the program to work with in order to reduce the influence
of potential signal fluctuations on the sensor input.
A new value is calculated using the following formula:
New value = old value * filter factor + raw value * (1 - filter factor)
Allocate physical analog inputs |
|||
Configuration > I/O allocation settings > Analog inputs |
|||
Analog inputs |
Device |
Position |
|
Outdoor temperature |
Controller |
AI4 |
|
Supply air temperature |
SA DPT (Exp 1) |
UI1 |
|
Room temperature |
Device 25 |
Temperature |
|
Extra sensor 1 |
Controller |
Select I/O |
|
... |
|||
↓ |
↓ |
↓ |
|
Click on the name or → to enter settings. Adjust the name and change the default state of the input if necessary. |
Select device used for this function. It can be either the Controller itself or one of the expansion modules. |
Select the actual physical input used for this function. |
|
↓ |
|||
Variable |
Available options & Selection |
Note |
|
Rename and change the default state if necessary |
|||
Configuration > I/O allocation settings > Analog inputs > Extra sensor 1 |
|||
Name |
[Extra sensor 1] > [Reception Temp] |
Changeable name |
|
Original name |
Extra sensor |
Unchangeable name |
|
Sensor type |
| Temperature | | Pressure | | Control signal | | Humidity | | CO2 | | Pressure for flow calculation | | Flow | |
- |
|
Signal type |
| PT1000 | 0-10V | |
- |
|
Filter factor |
[ 0.2 ] |
- |
|
Correction |
[ 0.0 ] |
- |
|