Access 5.x

Analog outputs




Allocate physical analog outputs

Configuration > I/O allocation settings > Analog outputs

Analog inputs

Device

Position

Heating (SEQ-A)

Controller

AO1

Exchanger (SEQ-B)

Controller

AO2

Supply air fan

Controller

AO3

Extract air fan

Controller

AO4

...



Click on the name or  to enter settings. Adjust the name and change the default state of the output if necessary.

Select device used for this function. It can be either the Controller itself or one of the expansion modules.

Select the actual physical output used for this function.





Variable

Available options & Selection

Note


Rename and change the default state if necessary

Configuration > I/O allocation settings > Analog outputs > Exchanger (SEQ-B)

Name

[Exchanger (SEQ-B)] > [EL. Heater]

Changeable name

Original name

Exchanger (SEQ-B)

Unchangeable name

Range output

| 0-10 V |

| 2-10 V |

| 10-2 V |

| 10-0 V |

| Vmin-Vmax |

| Vmax-Vmin |

-

Control signal at Vmin

0 %

Settings available if custom range output has been selected:

| Vmin-Vmax | or | Vmax-Vmin |

Control signal at Vmax

100 %

Min volt output (Vmin)

[2.5] V

Max volt output (Vmax)

[10.0] V