Access 5.x |
Analog outputs |
Allocate physical analog outputs |
|||
Configuration > I/O allocation settings > Analog outputs |
|||
Analog inputs |
Device |
Position |
|
Heating (SEQ-A) |
Controller |
AO1 |
|
Exchanger (SEQ-B) |
Controller |
AO2 |
|
Supply air fan |
Controller |
AO3 |
|
Extract air fan |
Controller |
AO4 |
|
... |
|||
↓ |
↓ |
↓ |
|
Click on the name or → to enter settings. Adjust the name and change the default state of the output if necessary. |
Select device used for this function. It can be either the Controller itself or one of the expansion modules. |
Select the actual physical output used for this function. |
|
↓ |
|||
Variable |
Available options & Selection |
Note |
|
Rename and change the default state if necessary |
|||
Configuration > I/O allocation settings > Analog outputs > Exchanger (SEQ-B) |
|||
Name |
[Exchanger (SEQ-B)] > [EL. Heater] |
Changeable name |
|
Original name |
Exchanger (SEQ-B) |
Unchangeable name |
|
Range output |
| 0-10 V | | 2-10 V | | 10-2 V | | 10-0 V | | Vmin-Vmax | | Vmax-Vmin | |
- |
|
Control signal at Vmin |
0 % |
Settings available if custom range output has been selected: | Vmin-Vmax | or | Vmax-Vmin | |
|
Control signal at Vmax |
100 % |
||
Min volt output (Vmin) |
[2.5] V |
||
Max volt output (Vmax) |
[10.0] V |
||