Access 4.x |
Component malfunction related alarms |
Configuration > Alarms > Component malfunction
ID |
Alarm name |
Alarm trigger |
1 |
Malfunction supply air fan 1 |
DI: Feedback supply air fan / Triggered from Modbus fan, if the fan is supposed to run but run indication can't be read out from the fan |
2 |
Malfunction supply air fan 2 |
Triggered from Modbus fan, if the fan is supposed to run but run indication can't be read out from the fan |
3 |
Malfunction supply air fan 3 |
Triggered from Modbus fan, if the fan is supposed to run but run indication can't be read out from the fan |
4 |
Malfunction supply air fan 4 |
Triggered from Modbus fan, if the fan is supposed to run but run indication can't be read out from the fan |
5 |
Malfunction supply air fan 5 |
Triggered from Modbus fan, if the fan is supposed to run but run indication can't be read out from the fan |
6 |
Malfunction extract air fan 1 |
DI: Feedback extract air fan / Triggered from Modbus fan, if the fan is supposed to run but run indication can't be read out from the fan |
7 |
Malfunction extract air fan 2 |
Triggered from Modbus fan, if the fan is supposed to run but run indication can't be read out from the fan |
8 |
Malfunction extract air fan 3 |
Triggered from Modbus fan, if the fan is supposed to run but run indication can't be read out from the fan |
9 |
Malfunction extract air fan 4 |
Triggered from Modbus fan, if the fan is supposed to run but run indication can't be read out from the fan |
10 |
Malfunction extract air fan 5 |
Triggered from Modbus fan, if the fan is supposed to run but run indication can't be read out from the fan |
11 |
Alarm supply air fan 1 |
Controller is reading (via internal modbus) internal alarm of the Supply air fan 1 |
12 |
Alarm supply air fan 2 |
Controller is reading (via internal modbus) internal alarm of the Supply air fan 2 |
13 |
Alarm supply air fan 3 |
Controller is reading (via internal modbus) internal alarm of the Supply air fan 3 |
14 |
Alarm supply air fan 4 |
Controller is reading (via internal modbus) internal alarm of the Supply air fan 4 |
15 |
Alarm supply air fan 5 |
Controller is reading (via internal modbus) internal alarm of the Supply air fan 5 |
16 |
Alarm extract air fan 1 |
Controller is reading (via internal modbus) internal alarm of the Extract air fan 1 |
17 |
Alarm extract air fan 2 |
Controller is reading (via internal modbus) internal alarm of the Extract air fan 2 |
18 |
Alarm extract air fan 3 |
Controller is reading (via internal modbus) internal alarm of the Extract air fan 3 |
19 |
Alarm extract air fan 4 |
Controller is reading (via internal modbus) internal alarm of the Extract air fan 4 |
20 |
Alarm extract air fan 5 |
Controller is reading (via internal modbus) internal alarm of the Extract air fan 5 |
35 |
Malfunction pump heater |
DI: Feedback heating (SEQ-A) |
36 |
Malfunction pump cooler |
DI: Feedback cooling (SEQ-C) |
37 |
Malfunction pump exchanger |
DI: Feedback exchanger (SEQ-B) |
38 |
Malfunction fire damper |
DI: Feedback fire damper. Fire damper exercise test failed |
39 |
Malfunction damper |
Damper has an internal warning or alarm |
43 |
Malfunction heating (SEQ-A) |
DI: Feedback heating (SEQ-A) |
44 |
Malfunction exchanger (SEQ-B) |
DI: Feedback exchanger (SEQ-B) |
45 |
Malfunction cooling (SEQ-C) |
DI: Feedback cooling (SEQ-C) |
46 |
Malfunction recirculation 1 (SEQ-D) |
DI: Feedback recirculation 1 (SEQ-D) |
47 |
Malfunction recirculation 2 (SEQ-E) |
DI: Feedback recirculation 2 (SEQ-E) |
48 |
Malfunction fan setpoint comp (SEQ-F) |
DI: Feedback fan setpoint comp (SEQ-F) |
49 |
Malfunction heating 2 (SEQ-G) |
DI: Feedback heating 2 (SEQ-G) |
50 |
Malfunction cooling 2 (SEQ-H) |
DI: Feedback cooling 2 (SEQ-H) |
51 |
Malfunction exchanger extract (SEQ-I) |
DI: Feedback exchanger extract (SEQ-I) |
52 |
Malfunction external heating/cooling (SEQ-J) |
DI: Feedback external heating/cooling (SEQ-J) |
67 |
Rotary exchanger alarm |
Exchanger rotation guard alarm |
78 |
Internal battery error |
Internal battery needs replacing |
144 |
Sensor error outdoor air temp |
Sensor faulty (Invalid reading) or missing |
145 |
Sensor error intake air temp |
Sensor faulty (Invalid reading) or missing |
146 |
Sensor error supply air temp |
Sensor faulty (Invalid reading) or missing |
147 |
Sensor error exhaust air temp |
Sensor faulty (Invalid reading) or missing |
148 |
Sensor error extract air temp |
Sensor faulty (Invalid reading) or missing |
149 |
Sensor error room temp 1 |
Sensor faulty (Invalid reading) or missing |
150 |
Sensor error room temp 2 |
Sensor faulty (Invalid reading) or missing |
151 |
Sensor error room temp 3 |
Sensor faulty (Invalid reading) or missing |
152 |
Sensor error room temp 4 |
Sensor faulty (Invalid reading) or missing |
153 |
Sensor error pressure supply air |
Sensor faulty (Invalid reading) or missing |
154 |
Sensor error pressure extract air |
Sensor faulty (Invalid reading) or missing |
155 |
Sensor error flow supply air |
Sensor faulty (Invalid reading) or missing |
156 |
Sensor error flow extract air |
Sensor faulty (Invalid reading) or missing |
157 |
Sensor error pressure exchanger supply air |
Sensor faulty (Invalid reading) or missing |
158 |
Sensor error pressure exchanger extract air |
Sensor faulty (Invalid reading) or missing |
159 |
Sensor error defrost temperature |
Sensor faulty (Invalid reading) or missing |
160 |
Sensor error frost protection 1 |
Sensor faulty (Invalid reading) or missing |
161 |
Sensor error frost protection 2 |
Sensor faulty (Invalid reading) or missing |
162 |
Sensor error frost protection 3 |
Sensor faulty (Invalid reading) or missing |
168 |
Signal error external control supply air fan |
Sensor faulty (Invalid reading) or missing |
169 |
Signal error external control extract air fan |
Sensor faulty (Invalid reading) or missing |
175 |
Sensor error external setpoint device temperature |
Sensor faulty (Invalid reading) or missing |
176 |
Signal error external flow setpoint |
Sensor faulty (Invalid reading) or missing |
177 |
Sensor error filter monitoring supply air |
Sensor faulty (Invalid reading) or missing |
178 |
Sensor error filter monitoring extract air |
Sensor faulty (Invalid reading) or missing |
179 |
Sensor error efficiency temperature |
Sensor faulty (Invalid reading) or missing |
180 |
Communication fault device |
Device on the bus is not responding |
182 |
Internal error |
Internal error in the controller |
185 |
Malfunction preheater |
DI: Feedback preheater |
186 |
Communication fault BMS master |
Triggered by BMS watchdog in case of communication interupt |
188 |
Sensor error preheater temperature |
Sensor faulty (Invalid reading) or missing |
189 |
Malfunction supply air fan 6 |
Triggered from Modbus fan, if the fan is supposed to run but run indication can't be read out from the fan |
190 |
Malfunction supply air fan 7 |
Triggered from Modbus fan, if the fan is supposed to run but run indication can't be read out from the fan |
191 |
Malfunction supply air fan 8 |
Triggered from Modbus fan, if the fan is supposed to run but run indication can't be read out from the fan |
192 |
Malfunction extract air fan 6 |
Triggered from Modbus fan, if the fan is supposed to run but run indication can't be read out from the fan |
193 |
Malfunction extract air fan 7 |
Triggered from Modbus fan, if the fan is supposed to run but run indication can't be read out from the fan |
194 |
Malfunction extract air fan 8 |
Triggered from Modbus fan, if the fan is supposed to run but run indication can't be read out from the fan |
195 |
Alarm supply air fan 6 |
Controller is reading (via internal modbus) internal alarm of the Supply air fan 6 |
196 |
Alarm supply air fan 7 |
Controller is reading (via internal modbus) internal alarm of the Supply air fan 7 |
197 |
Alarm supply air fan 8 |
Controller is reading (via internal modbus) internal alarm of the Supply air fan 8 |
198 |
Alarm extract air fan 6 |
Controller is reading (via internal modbus) internal alarm of the Extract air fan 6 |
199 |
Alarm extract air fan 7 |
Controller is reading (via internal modbus) internal alarm of the Extract air fan 7 |
200 |
Alarm extract air fan 8 |
Controller is reading (via internal modbus) internal alarm of the Extract air fan 8 |
207 |
Malfunction heating zone 1 |
DI: Feedback heating zone 1 |
208 |
Malfunction heating zone 2 |
DI: Feedback heating zone 2 |
209 |
Malfunction heating zone 3 |
DI: Feedback heating zone 3 |
210 |
Malfunction cooling zone 1 |
DI: Feedback cooling zone 1 |
211 |
Malfunction cooling zone 2 |
DI: Feedback cooling zone 2 |
212 |
Malfunction cooling zone 3 |
DI: Feedback cooling zone 3 |
222 |
Sensor error supply air temp zone 1 |
Sensor faulty (Invalid reading) or missing |
223 |
Sensor error supply air temp zone 2 |
Sensor faulty (Invalid reading) or missing |
224 |
Sensor error supply air temp zone 3 |
Sensor faulty (Invalid reading) or missing |
225 |
Sensor error room temp zone 1 |
Sensor faulty (Invalid reading) or missing |
226 |
Sensor error room temp zone 2 |
Sensor faulty (Invalid reading) or missing |
227 |
Sensor error room temp zone 3 |
Sensor faulty (Invalid reading) or missing |
228 |
Sensor error extract temp zone 1 |
Sensor faulty (Invalid reading) or missing |
229 |
Sensor error extract temp zone 2 |
Sensor faulty (Invalid reading) or missing |
230 |
Sensor error extract temp zone 3 |
Sensor faulty (Invalid reading) or missing |
231 |
Sensor error freeze protection zone 1 |
Sensor faulty (Invalid reading) or missing |
232 |
Sensor error freeze protection zone 2 |
Sensor faulty (Invalid reading) or missing |
233 |
Sensor error freeze protection zone 3 |
Sensor faulty (Invalid reading) or missing |
237 |
Device warning |
Controller is reading (via internal modbus) internal warning of the device |
238 |
Device alarm |
Controller is reading (via internal modbus) internal alarm of the device |