Access 4.x |
Manual operation and malfunction warnings |
Configuration > Alarms > Manual operation and warnings
ID |
Alarm name |
Alarm trigger |
21 |
Warning supply air fan 1 |
Controller is reading (via internal modbus) internal warning of the Supply air fan 1 |
22 |
Warning supply air fan 2 |
Controller is reading (via internal modbus) internal warning of the Supply air fan 2 |
23 |
Warning supply air fan 3 |
Controller is reading (via internal modbus) internal warning of the Supply air fan 3 |
24 |
Warning supply air fan 4 |
Controller is reading (via internal modbus) internal warning of the Supply air fan 4 |
25 |
Warning supply air fan 5 |
Controller is reading (via internal modbus) internal warning of the Supply air fan 5 |
26 |
Warning extract air fan 1 |
Controller is reading (via internal modbus) internal warning of the Extract air fan 1 |
27 |
Warning extract air fan 2 |
Controller is reading (via internal modbus) internal warning of the Extract air fan 2 |
28 |
Warning extract air fan 3 |
Controller is reading (via internal modbus) internal warning of the Extract air fan 3 |
29 |
Warning extract air fan 4 |
Controller is reading (via internal modbus) internal warning of the Extract air fan 4 |
30 |
Warning extract air fan 5 |
Controller is reading (via internal modbus) internal warning of the Extract air fan 5 |
31 |
External operation supply air fan |
fan is running (run indication) but it is not started by the application |
32 |
External operation extract air fan |
fan is running (run indication) but it is not started by the application |
62 |
Service stop |
Service stop activated |
64 |
Warning freeze protection |
Frost protection function is overriding the control of the heater output (description of the function) |
80 |
Restart blocked after power on |
Restart blocked due to earlier power failure |
113 |
Manual operation air handling unit |
Manual operation |
114 |
Manual operation supply air |
Manual operation |
115 |
Manual operation supply air fan |
Manual operation |
116 |
Manual operation extract air fan |
Manual operation |
117 |
Manual operation heater |
Manual operation |
118 |
Manual operation exchanger |
Manual operation |
119 |
Manual operation cooler |
Manual operation |
120 |
Manual operation damper |
Manual operation |
121 |
Manual operation pump heater |
Manual operation |
122 |
Manual operation pump exchanger |
Manual operation |
123 |
Manual operation pump cooler |
Manual operation |
124 |
Manual operation damper recirculation |
Manual operation |
125 |
Manual operation damper outdoor air |
Manual operation |
126 |
Manual operation damper exhaust air |
Manual operation |
127 |
Manual operation fire damper |
Manual operation |
128 |
Manual control heating (SEQ-A) |
Manual operation |
129 |
Manual control exchanger (SEQ-B) |
Manual operation |
130 |
Manual control cooling (SEQ-C) |
Manual operation |
131 |
Manual control recirculation 1 (SEQ-D) |
Manual operation |
132 |
Manual control recirculation 2 (SEQ-E) |
Manual operation |
133 |
Manual control fan setpoint opmp (SEQ-F) |
Manual operation |
134 |
Manual control heating 2 (SEQ-G) |
Manual operation |
135 |
Manual control cooling 2 (SEQ-H) |
Manual operation |
136 |
Manual control exchanger extract (SEQ-I) |
Manual operation |
137 |
Manual control external heating/cooling |
Manual operation |
138 |
Output in manual operation |
Manual operation |
139 |
Input in manual operation |
Manual operation |
140 |
Manual operation extra controller |
Manual operation |
141 |
Manual operation external fan motor 1 |
Manual operation |
142 |
Manual operation external fan motor 2 |
Manual operation |
143 |
Manual operation pretreatment |
Manual operation |
201 |
Warning supply air fan 6 |
Controller is reading (via internal modbus) internal warning of the Supply air fan 6 |
202 |
Warning supply air fan 7 |
Controller is reading (via internal modbus) internal warning of the Supply air fan 7 |
203 |
Warning supply air fan 8 |
Controller is reading (via internal modbus) internal warning of the Supply air fan 8 |
204 |
Warning extract air fan 6 |
Controller is reading (via internal modbus) internal warning of the Extract air fan 6 |
205 |
Warning extract air fan 7 |
Controller is reading (via internal modbus) internal warning of the Extract air fan 7 |
206 |
Warning extract air fan 8 |
Controller is reading (via internal modbus) internal warning of the Extract air fan 8 |