Access 4.x

Extra alarm


The Access can handle up to ten extra alarms triggered via dedicated digital inputs. Extra alarms are configurable the same way as all the standard alarms: They can be assigned to A, B or C alarm class and set for action (See "Configuring alarms").


Configuration of the extra alarms


Variable

Available options & Selection

Note


Number of extra alarms

Configuration > Functions > Extra sensors & inputs

Extra alarms

| Off | 1 | 2 | 3 | ... | 10 |

Select number of extra alarms in use


Allocate digital input

Configuration > I/O allocation settings > Digital inputs >

Extra alarm 1

Any available I/O



Configure alarm

Configuration > Alarms > Extra sensors and alarms >

Extra alarm 1 (68)

Multiple settings

See "Configuring alarms"



Chapter info                              

Last reviewed: 9/3/2021

Access version: 4.5-1-01 (2913)