Access 5.x |
Control modes > Extract air dependent supply air |
Setpoint of the supply air temperature follow the extract air temperature with a difference.
Supply air temperature setpoint = extract air temperature + difference.
Settings and configuration for Extract air dependent of supply air control |
|||
Variable |
Available options & Selection |
Note |
|
Activate temperature control type |
|||
Configuration > Functions > Function activation |
|||
Temperature control type |
|...| Extract air dependent supply air | |
- |
|
Activate sensors & additional options |
|||
Configuration > Functions > Temperature control |
|||
Extract air temperature sensor |
|Yes | No | |
- |
|
Supply air temperature sensor |
|Yes | No | |
- |
|
Configure inputs |
|||
Configuration > I/O allocation settings > Analog inputs > |
|||
Extract air temperature sensor |
Any available I/O |
||
Supply air temperature sensor |
|||
Operational settings |
|||
Data & Settings > Temperature control > Supply air controller |
|||
Supply air temperature |
__ oC |
Actual supply air temperature |
|
Setpoint delta T extract air - supply air |
[-2.0] oC |
[default: supply air is set to be colder by 2 degrees than extract air ] |
|
Min limit supply air |
[12.0] oC |
Limits of the supply air temperature. |
|
Max limit supply air |
[30.0] oC |
||
Actual setpoint supply air |
__ oC |