Access 5.x  | 
Control modes > Extract air dependent supply air  | 
Setpoint of the supply air temperature follow the extract air temperature with a difference.
Supply air temperature setpoint = extract air temperature + difference.
Settings and configuration for Extract air dependent of supply air control  | 
|||
Variable  | 
Available options & Selection  | 
Note  | 
|
Activate temperature control type  | 
|||
Configuration > Functions > Function activation  | 
|||
Temperature control type  | 
|...| Extract air dependent supply air |  | 
-  | 
|
Activate sensors & additional options  | 
|||
Configuration > Functions > Temperature control  | 
|||
Extract air temperature sensor  | 
|Yes | No |  | 
-  | 
|
Supply air temperature sensor  | 
|Yes | No |  | 
-  | 
|
Configure inputs  | 
|||
Configuration > I/O allocation settings > Analog inputs >  | 
|||
Extract air temperature sensor  | 
Any available I/O  | 
||
Supply air temperature sensor  | 
|||
Operational settings  | 
|||
Data & Settings > Temperature control > Supply air controller  | 
|||
Supply air temperature  | 
__ oC  | 
Actual supply air temperature  | 
|
Setpoint delta T extract air - supply air  | 
[-2.0] oC  | 
[default: supply air is set to be colder by 2 degrees than extract air ]  | 
|
Min limit supply air  | 
[12.0] oC  | 
Limits of the supply air temperature.  | 
|
Max limit supply air  | 
[30.0] oC  | 
||
Actual setpoint supply air  | 
__ oC  | 
||