Access 4.x |
Fail safe |
The fail-safe function ensures continuity of AHU operation if malfunction of pressure transmitters or supply temperature sensor occurs.
In the fail-safe mode, control of the fan and sequence is overridden with the manual output. The mode can only be active during scheduled run period and in absence of critical alarms (e.g. Freezing protection, Fire alarm). The AHU returns to normal operation once connection to the faulty sensor is restored.
In case of malfunction of the supply air temperature sensor (AL146) the fail-safe mode can override output of Heating or Cooling sequences. It also overrides all the sequences of the higher priority to the max output.
e.g. fail-safe is configured to set the 3rd Heating sequence to 50% in case of sensor malfunction. This means that the heating sequences will be set accordingly:
1st heating sequence "Heating 1" = 100%
2nd heating sequence "Heating 2" = 100%
3rd heating sequence "Heating 3" = 50%
The fail-safe mode is indicated by the alarm AL241 Fail-safe airflow/temperature control.
Manual output of the supply air fan can be triggered by:
AL153 Sensor error pressure supply air (if Pressure is set as fan control type)
AL155 Sensor error flow supply air (if Flow is set as fan control type)
Manual output of the extract air fan can be triggered by:
AL154 Sensor error pressure extract air (if Pressure is set as fan control type)
AL156 Sensor error flow extract air (if Flow is set as fan control type)
Manual output of the sequence can be triggered by:
AL146 Sensor error supply air temperature
Configuration example of fail-safe mode |
|||||||
Variable |
Available options & Selection |
Note |
|||||
Activate Fail-safe mode |
|||||||
Configuration > Functions > Function activation |
|||||||
Fail-safe mode |
| No | Yes | |
- |
|||||
Enable fail-safe for the alarms |
|||||||
Configuration > Alarms > Manual operation and warnings > 146 Sensor error supply air temperature |
|||||||
Action |
… | Fail-safe mode | |
- |
|||||
Configuration > Alarms > Manual operation and warnings > 153 Sensor error pressure supply air |
|||||||
Action |
… | Fail-safe mode | |
Can also be set for AL155 |
|||||
Configuration > Alarms > Manual operation and warnings > 154 Sensor error pressure extract air |
|||||||
Action |
… | Fail-safe mode | |
Can also be set for AL156 |
|||||
Configure manual outputs in Fail-safe mode |
|||||||
Configuration > Functions > Fail-safe mode |
|||||||
153 - Sensor error pressure supply air |
[0] % |
Set fail-safe manual output of the SAF |
|||||
Supply air fan output in fail-safe mode |
|||||||
154 - Sensor error flow extract air |
[0] % |
Set fail-safe manual output of the EAF |
|||||
Extract air fan output in fail-safe mode |
|||||||
146 - Sensor error supply air temperature |
| Off | Heating 1 | … | Heating 10 | |
Select and set Fail-safe manual output of the sequence. Heating 1 - 1st heating sequence Heating 2 - 2nd heating sequence … |
|||||
Supply air temperature control in fail-safe mode - Heating |
|||||||
Output in fail-safe mode |
[0] % |
Chapter info
Last reviewed: 09/12/2021
Access version: 4.6-1-00 (3068)