Guard type filter monitor
Access 4.5 and later releases |
Guard type filter monitor |
Filter guard utilizes pressure switches set for the specific pressure difference over the filter.
Configuration and settings for guard type filter monitoring |
|||
Variable |
Available options & Selection |
Note |
|
Activate filter monitoring function |
|||
Configuration > Functions > Function activation |
|||
Filter monitoring |
| Yes | No | |
||
Configuration of filter monitoring function |
|||
Configuration > Functions > Filter monitoring |
|||
Supply air pre-filter |
| No | Sensor | Guard | |
Enable filters by selecting filter monitor type |
|
Supply air filter |
| No | Sensor | Guard | |
||
Supply air end-filter |
| No | Sensor | Guard | |
||
Extract air pre-filter |
| No | Sensor | Guard | |
||
Extract air filter |
| No | Sensor | Guard | |
||
Filter classification setup |
> |
Filter calibration related settings |
|
Reset sevice interval times |
| Yes | No | |
Periodic service related settings |
|
Service interval |
[0] months |
||
Configure inputs |
|||
Configuration > I/O allocation settings > Digital inputs > |
|||
Pre-filter guard supply air |
Any available I/O |
Configure digital inputs the pressure switches are connected to |
|
Filter guard supply air |
|||
End-filter guard supply air |
|||
Pre-filter guard extract air |
|||
Filter guard extract air |
|||
Filter alarms |
|||
Configuration > Alarms > Air and temperature control > |
|||
AL53 Filter alarm supply air |
> |
Adjust alarm settings if necessary |
|
AL54 Filter alarm extract air |
> |
||
AL242 Pre-filter alarm supply air |
> |
||
AL243 End filter alarm supply air |
> |
||
AL244 Pre-filter alarm extract air |
> |