|
Access 5.x |
Humidification |
Access can humidify the supply air by regulating the output of a single-stage humidifier. The supply-air humidification is controlled via a PID loop to increase the room (or extract-air) relative humidity to the setpoint value. An analog output is used to modulate the humidifier capacity, increasing the output when room (or extract-air) humidity decreases. A digital output can also be used to start the humidifier.
Supply-air humidification can be monitored and limited by installing an optional RH duct sensor and configuring the appropriate settings. The limitation is defined by “Max limit humidity supply air” and “Hysteresis for max limit humidity supply air”:
For example, if the maximum limit is set to 80% RH and the hysteresis to 20% RH, the controller output will begin to decrease at 60% RH. At the midpoint between 60% and 80% RH (i.e., 70% RH), the controller output will be reduced by 50%. If the duct humidity still reaches 80% RH, the output will be fully reduced.
Humidification is disabled during cool-down mode to allow the humidifier to dry before shutdown.
Configuration example of the humidification |
|||
Variable |
Available options & Selection |
Note |
|
Activate Humidity control |
|||
Configuration > Functions > Function activation |
|||
Humidity control |
… | Humidification |… |
||
Configure function |
|||
Configuration > Functions > Humidity control |
|||
Humidity control |
Humidification |
Indication of what function has been activated |
|
Type of output |
| Analog | Step | Analog + Step | |
| Analog | - 0..10V signal for capacity |Step| - relay output for start/stop |
|
PID Settings |
|||
Configuration > PID controllers > Humidification |
|||
P-band |
[100] %RH |
PID settings to describe responsiveness of the humidifier |
|
I-time |
[300] s |
||
D-time |
[0] s |
||
PID output max limit |
[100] % |
Max output of the PID can be limited |
|
Hardwired interface |
|||
Configuration > I/O allocation settings > |
|||
Analog inputs > Humidity room/extract air |
Any available I/O |
Mandatory - humidity sensor for reference |
|
Analog inputs > Humidity supply air |
Optional - for limiting humidity of the supply air |
||
Digital outputs > Humidity control start |
Interface to the humidifier |
||
Analog outputs > Humidity control |
|||
Operational settings |
|||
Data & Settings > Humidity control |
|||
Humidity room/extract air |
__ % |
Actual measured RH |
|
Setpoint humidity room/extract |
[50] %RH |
||
Max limit humidity supply air |
[80] %RH |
Limiting of the supply air humidity |
|
Hysteresis for max limit humidity supply air |
[20] %RH |
||
Digital output start point |
[15] % |
DO (Humidity control start) is activated once AO (Humidity control) exceeds 15% |
|
Digital output stop point |
[5] % |
DO (Humidity control start) is deactivated once AO (Humidity control) falls bellow 5% |
|
Operation overview |
|||
Data & Settings > Operation overview > Humidity |
|||
Humidity room/extract air |
__ % |
Overview of the function in action |
|
Humidity supply air |
__ % |
||
Setpoint humidity room/extract |
[50] %RH |
||
Humidification setpoint |
__ % |
||
Humidity control start |
Off | On |
||
Humidity control mode |
Not active | Humidification |
||
