Access 4.x |
Humidification + Dehumidification |
The combined mode utilizes both: Humidification and override of the temperature sequence for dehumidification. The setpoint for desired room/extract air humidity is used as a reference for two new setpoints: "Humidification setpoint" and "Dehumidification setpoint". The setpoints are separated by the neutral zone.
Configuration example of combined humidification + dehumidification |
|||
Variable |
Available options & Selection |
Note |
|
Activate Humidity control |
|||
Configuration > Functions > Function activation |
|||
Humidity control |
… | Humidification + Dehumidification | |
||
Configure function |
|||
Configuration > Functions > Humidity control |
|||
Humidity control |
Humidification + Dehumidification |
Indication of what function has been activated |
|
Select sequence for dehumidify |
... | Cooling |... |
Sequence to override for dehumidification |
|
Type of output |
| Analog | Step | Analog + Step | |
| Analog | - 0..10V signal for capacity | Step| - relay output for start/stop |
|
Neutral zone type |
| 1/2 neutral zone | | Neutral zone to dehumidification | | Neutral zone to humidification | |
||
PID Settings |
|||
Configuration > PID controllers > Humidification |
|||
P-band |
[100] %RH |
PID settings to describe responsiveness of the humidifier |
|
I-time |
[300] s |
||
D-time |
[0] s |
||
PID output max limit |
[100] % |
max output of the PID can be limited |
|
Configuration > PID controllers > Dehumidification |
|||
P-band |
[100] %RH |
PID settings for dehumidification signal |
|
I-time |
[300] s |
||
D-time |
[0] s |
||
PID output max limit |
[100] % |
max output of the PID can be limited |
|
Hardwired interface |
|||
Configuration > I/O allocation settings > |
|||
Analog inputs > Humidity room/extract air |
Any available I/O |
Mandatory - humidity sensor for reference |
|
Analog inputs > Humidity supply air |
Optional - for limiting humidity of the supply air |
||
Digital outputs > Humidity control start |
Interface to the humidifier |
||
Analog outputs > Humidity control |
|||
Operational settings |
|||
Data & Settings > Humidity control |
|||
Humidity room/extract air |
__ % |
Actual measured RH |
|
Setpoint humidity room/extract |
[50] %RH |
||
Neutral zone extract/room |
[20] %RH |
||
Dehumidification setpoint |
__ %RH |
The new setpoint created out of main setpoint and neutral zone |
|
Humidification setpoint |
__ %RH |
||
Max limit humidity supply air |
[80] %RH |
Limiting of the supply air humidity |
|
Hysteresis for max limit humidity supply air |
[20] %RH |
||
Digital output start point |
[15] % |
DO (Humidity control start) is activated once AO (Humidity control) exceeds 15% |
|
Digital output stop point |
[5] % |
DO (Humidity control start) is deactivated once AO (Humidity control) falls below 5% |
|
Operation overview |
|||
Data & Settings > Operation overview > Humidity |
|||
Humidity room/extract air |
__ % |
Overview of the function in action |
|
Setpoint humidity room/extract |
[50] %RH |
||
Dehumidification setpoint |
__ %RH |
||
Humidification setpoint |
__ %RH |
||
Humidity control |
__ % |
||
Humidity control start |
Off | On |
||
Humidity control mode |
|Not active | | Humidification | | Dehumidification | |