Access 5.3

Reversible HP Supply air - Extract air





Variable

Available options & Selection

Note


Enable and configure Heat pump sequences

Configuration > Functions > Function activation > Heating/Cooling sequence setup > SEQ-G Heating 2

Name

Heating 2


Type of sequence

| Heating |

Type of heater

| DX |

...


Configuration > Functions > Function activation > Heating/Cooling sequence setup > SEQ-H Cooling 2

Name

Cooling 2


Type of sequence

| Cooling |

Type of heater

| DX |

...



Combine Heat pump sequences under changeover function

Configuration > Functions > Function activation > Heating/Cooling sequence setup > Changeover 1

Name

Changeover 1


Changeover sequence for heating

Heating 2

Changeover sequence for cooling

Cooling 2

Type of changeover

| Reversible heat pump Supply air-Extract air |


Configuration of Modbus connected Heat pump

Configuration > System settings > Communication Devices > Device 20

Type

| Heat pump |

Select type of the connected device (Heat pump)

Brand

| 1 Circuit | 1 Circuit with Boost heater | 2 Circuit | 2 Circuit with Boost heater |

Select type of the Heat pump

Refrigerant type

| R410A | R454B |

Select type of refrigerant used in the HP

Address

[0] > [54]

Enter the same address as configured in the Heat pump

Function

| Select | Exp1 | Exp2 | Exp3 |...

Assign function (Spare expansion unit number)

Heat pump sequence

| Changeover 1 |

Select the changeover sequence to be related to the operation of the heat pump

Name

[Device 20] > [Heat pump]

Change default name to more informative

Communication type

| RTU | TCP |

-

Communication port

| Ext-link | BMS | Int-link 1 & 2 |

Select port for communication to the device


Heat pump configuration

Configuration > Functions > Heat pump

Heat pump request mode

| Reversible | Only cooling | Only heating |


Increase air flow extract air fan to avoid heat pump - high pressure alarm

| No | Auto |


Heat pump reduce mode - delay time before next sequence

[60] s


Boost heater capacity

[0.0] kW


Compensation offset curves ->

Frosting prevention function to increase heating capacity in the lower air flow range and low temperatures (see table bellow)

Gas evacuation setup ->

Function available if R454B or R290 is selected as refrigerant type









Variable

Available options & Selection

Note


Heat pump configuration

Configuration > Functions > Heat pump > Flow compensation curve ->

Max total compensation

[-2.5]

   

Actual compensation

0


Flow compensation curve

Flow

Compensation

Reduction of pressure in the Heat pump refrigerant system at low air flow

Lowest points

[2000] m3/h

[-1.1] bar

Middle points

[4160] m3/h

[-0.5] bar

Highest points

[6318] m3/h

[0.0] bar

Exchanger-outdoor compensation curve

Temperature

Compensation

Reduction of pressure in the Heat pump refrigerant system at low outdoor air temperature

Lowest points

[-20] oC

[0.0] bar

Middle points

[-10] oC

[-1.3] bar

Highest points

[0] oC

[-2.0] bar