Access 5.3 |
Reversible HP Supply air - Extract air |
Variable |
Available options & Selection |
Note |
|
Enable and configure Heat pump sequences |
|||
Configuration > Functions > Function activation > Heating/Cooling sequence setup > SEQ-G Heating 2 |
|||
Name |
Heating 2 |
||
Type of sequence |
| Heating | |
||
Type of heater |
| DX | |
||
... |
|||
Configuration > Functions > Function activation > Heating/Cooling sequence setup > SEQ-H Cooling 2 |
|||
Name |
Cooling 2 |
||
Type of sequence |
| Cooling | |
||
Type of heater |
| DX | |
||
... |
|||
Combine Heat pump sequences under changeover function |
|||
Configuration > Functions > Function activation > Heating/Cooling sequence setup > Changeover 1 |
|||
Name |
Changeover 1 |
||
Changeover sequence for heating |
Heating 2 |
||
Changeover sequence for cooling |
Cooling 2 |
||
Type of changeover |
| Reversible heat pump Supply air-Extract air | |
||
Configuration of Modbus connected Heat pump |
|||
Configuration > System settings > Communication Devices > Device 20 |
|||
Type |
| Heat pump | |
Select type of the connected device (Heat pump) |
|
Brand |
| 1 Circuit | 1 Circuit with Boost heater | 2 Circuit | 2 Circuit with Boost heater | |
Select type of the Heat pump |
|
Refrigerant type |
| R410A | R454B | |
Select type of refrigerant used in the HP |
|
Address |
[0] > [54] |
Enter the same address as configured in the Heat pump |
|
Function |
| Select | Exp1 | Exp2 | Exp3 |... |
Assign function (Spare expansion unit number) |
|
Heat pump sequence |
| Changeover 1 | |
Select the changeover sequence to be related to the operation of the heat pump |
|
Name |
[Device 20] > [Heat pump] |
Change default name to more informative |
|
Communication type |
| RTU | TCP | |
- |
|
Communication port |
| Ext-link | BMS | Int-link 1 & 2 | |
Select port for communication to the device |
|
Heat pump configuration |
|||
Configuration > Functions > Heat pump |
|||
Heat pump request mode |
| Reversible | Only cooling | Only heating | |
||
Increase air flow extract air fan to avoid heat pump - high pressure alarm |
| No | Auto | |
||
Heat pump reduce mode - delay time before next sequence |
[60] s |
||
Boost heater capacity |
[0.0] kW |
||
Compensation offset curves -> |
Frosting prevention function to increase heating capacity in the lower air flow range and low temperatures (see table bellow) |
||
Gas evacuation setup -> |
Function available if R454B or R290 is selected as refrigerant type |
||
Variable |
Available options & Selection |
Note |
||
Heat pump configuration |
||||
Configuration > Functions > Heat pump > Flow compensation curve -> |
||||
Max total compensation |
[-2.5] |
|
||
Actual compensation |
0 |
|||
Flow compensation curve |
Flow |
Compensation |
Reduction of pressure in the Heat pump refrigerant system at low air flow |
|
Lowest points |
[2000] m3/h |
[-1.1] bar |
||
Middle points |
[4160] m3/h |
[-0.5] bar |
||
Highest points |
[6318] m3/h |
[0.0] bar |
||
Exchanger-outdoor compensation curve |
Temperature |
Compensation |
Reduction of pressure in the Heat pump refrigerant system at low outdoor air temperature |
|
Lowest points |
[-20] oC |
[0.0] bar |
||
Middle points |
[-10] oC |
[-1.3] bar |
||
Highest points |
[0] oC |
[-2.0] bar |
||