Access 5.x |
Setting of the modbus connection to the room unit (ED-RUD) |
Example of setting connection and the button functions for the ED-RUD Room controller |
|||
Variable |
Available options & Selection |
Note |
|
Configure port communication settings |
|||
Configuration > System settings > Communication > Communication port: Ext-link |
|||
Function |
... | Modbus master | ... |
Set function of the port the Room unit is physically connected |
|
Configuring connection to the room controller |
|||
Configuration > System settings > Communication Devices > Device 25 |
|||
Type |
...| Room unit | … |
Select type of the connected device (Room unit) |
|
Brand |
| ED-RUD (Modbus) | |
Select ED-RUD (Modbus) |
|
Address |
[0] > [41] |
Enter the same address as configured in the ED-RUD room unit |
|
Function |
... | Exp5 | ... |
Assign function (any available expansion unit) |
|
Fan button function |
| No function | Change fan speed | Change fan speed as extended operation | |
Select the "Fan button" push action |
|
Idle view function |
| Room temperature | Setpoint | |
The information shown on the screen while ED-RUD is in idle mode |
|
Setpoint temperature control |
| Main unit | Temperature zone 1 | Temperature zone 2 | Temperature zone 3 | |
Select which temperature setpoint is adjusted with the room unit |
|
Setpoint adjustment |
| No adjustment | Adjustment with 0.5oC | Adjustment with 1oC | |
The accuracy of setpoint adjustment |
|
Name |
[Device 25] > [Room unit] |
Change default name to the more informative |
|
Communication type |
| RTU | TCP | |
- |
|
Communication port |
| Ext-link | BMS | Int-link 1 & 2 | |
Select port for communication to the device |
Tip: Check device status after configuration