Access 5.x

Reversible coil with water


The reversible water coil (a.k.a. Changeover or Combi coil) is an external water coil, used for seasonal heating or cooling of the supply air.

It operates in either heating or cooling mode depending on the season, supplied by a reversible heat pump or central plant. Only one mode is active at a time.

Performance of the reversible water coil is controlled from the main AHU's controller (Access) through hardwired components:

Valve actuator (AO signal for flow adjustment)

Pump control (DO signal for pump start/stop)

Indication of mode (DI signal from external heating/cooling system to the AHU is telling if hat water for heating or cold water for cooling is available)

Flow of the heating / cooling medium is controlled by valve actuator.


Reversible coil with water (configuration example)


Variable

Available options & Selection

Note


Enable and configure Heat pump sequences

Configuration > Functions > Function activation > Heating/Cooling sequence setup > SEQ-G Heating 2

Name

Heating 2

The "Heating 2" sequence set as Combi coil type heater. Freeze protection and other relevant settings can be enabled if necessary

Type of sequence

| Heating |

Type of heater

| Combi coil |

Type of freeze protection

| Temperature sensor |

Freeze protection sensor

| Freeze protection temperature 1 |

...


Configuration > Functions > Function activation > Heating/Cooling sequence setup > SEQ-H Cooling 2

Name

Cooling 2

The "Cooling 2" sequence set as water type cooler. Additional settings for indication can be enabled if necessary

Type of sequence

| Cooling |

Type of cooler

| Water |

...



Combine Heat pump sequences under changeover function


Configuration > Functions > Function activation > Heating/Cooling sequence setup > Changeover 2

Name

Changeover 2

The "Heating 2" and "Cooling 2" sequences shall be combined under "Changeover 2" function. Changeover type set to "Combi coil"

Changeover sequence for heating

| Heating 2 |

Changeover sequence for cooling

| Cooling 2 |

Type of changeover

| Combi coil water (1x valve + 1x pump) |


Interface to the zone sensors and valves

Configuration > I/O allocation settings >

Analog inputs > Freeze protection temperature 1

Any available input / output

Immersion or contact temperature sensor for the freeze protection

Digital inputs > Cooling/(Heating) changeover 2

Indication for the Access if HOT or COLD water is available

Analog outputs > Changeover 2

Valve control

Digital outputs > Changeover 2

Indication that function is active (might be used for starting/stopping pump)