Sum alarm output |
Sum alarm indication activates digital output in case of active alarms of the particular alarm class. Two digital outputs for the alarm class indication are available:
- DO: Sum alarm 1 - indication of the A class alarms / indication A and B class alarms
- DO: Sum alarm 2 - indication of the B class alarms / indication B and C class alarms
Sum alarm indication is reset once the active alarms are acknowledged.
Example of setting sum alarm indication |
|||
Variable |
Available options & Selection |
Note |
|
Activating Sum alarm indication |
|||
Configuration > Functions > Extra indications & outputs |
|||
Sum alarm outputs |
| No | |
- |
|
| A/B-alarm | |
Sum alarm 1 for A or B class alarms |
||
| A-alarm + B-alarm | |
Sum alarm 1 for A class alarms Sum alarm 2 for B class alarms |
||
| A-alarm + B/C-alarm | |
Sum alarm 1 for A class alarms Sum alarm 2 for B and C class alarms |
||
IO allocation |
|||
Configuration > I/O allocation settings > Digital outputs |
|||
Sum alarm 1 |
Any available I/O |
Indicating A class alarms |
|
Sum alarm 2 |
Indicating B and C class alarms |
Related topics
Auxiliary indication (for a specific alarm)