Access 4.x |
Fan control Type: Supply air pressure and extract air fan slave (configuration example) |
Configuration of "Supply air pressure and extract air fan slave" control type |
|||
Variable |
Available options & Selection |
Note |
|
Activation of fan control functions |
|||
Configuration > Functions > Function activation > |
|||
Fan control type |
...| Supply air pressure with extract air fan slave |… |
||
Fan levels |
... | Low-Normal | ... |
Choice of fan levels to be used |
|
Fan configuration |
|||
Configuration > Functions > Fan control |
|||
Fan |
| Supply air + Extract air | ... |
Choice of fan combination |
|
Type of feedback supply air fan |
| None | Alarm | Run Indication | |
Function of the digital input of the fan feedback. Tripping of the digital input activates the alarm "AL-1" or "AL-6" |
|
Type of feedback extract air fan |
| None | Alarm | Run Indication | |
||
PID settings |
|||
Configuration > PID controllers > Supply air fan |
|||
P-band |
[500] Pa |
PID settings of the supply air fan |
|
I-time |
[60] s |
||
D-time |
[0] s |
||
Configuration > PID controllers > Extract air fan |
|||
P-band |
[500] Pa |
PID settings of the extract air fan |
|
I-time |
[60] s |
||
D-time |
[0] s |
||
Interface to the fans and pressure transmitters |
|||
Configuration > I/O allocation settings > |
|||
Analog inputs > Pressure supply air |
Any available I/O |
Measuring of the supply air duct pressure |
|
Digital inputs > Feedback supply air fan |
Start, speed and feedback signals to hardwired fans. These IOs can stay unconfigured for modbus fans. |
||
Digital inputs > Feedback extract air fan |
|||
Analog outputs > Supply air fan |
|||
Analog outputs > Extract air fan |
|||
Digital outputs > Supply air fan start |
|||
Digital outputs > Extract air fan start |
|||
Fan setpoints |
|||
Data & Settings > Fan control > Fan setpoints |
|||
Setpoint low speed supply air fan |
[250] Pa |
Change default setpoint values of the fan levels |
|
Setpoint normal speed supply air fan |
[500] Pa |
||
Slave factor |
[1.0] |
Adjusted if EAF has different characteristics then SAF |
|
Operational settings |
|||
Data & Settings > Fan control > Supply air fan |
|||
Start delay |
[60] s |
Delay of fan start and stop at starting and stopping of the unit |
|
Stop delay |
[180] s |
||
Outdoor air damper stop delay |
[0] s |
Damper closing delay for avoiding over-pressure at fan stop |
|
Min pressure for supply air fan indication |
[25] Pa |
Minimal pressure in the duct to indicate that the fan is running. Otherwise "AL-1 Malfunction supply air fan" is triggered |
|
Data & Settings > Fan control > Extract air fan |
|||
Start delay |
[0] s |
Delay of fan start and stop at starting and stopping of the unit |
|
Stop delay |
[30] s |
||
Exhaust air damper stop delay |
[0] s |
Damper closing delay for avoiding over-pressure at fan stop |
|
Run schedule |
|||
Time settings > Schedule |
|||
Fan Low Speed |
> |
Run schedule for each fan level |
|
Fan Normal Speed |
> |
Related topics: