Zone control: Room cascade configuration example |
Ventilated premises is a shop-floor with a office inside it. Office zone requires additional heating and cooling to maintain comfort temperature.
Output of the office heater/cooler is being controlled by the zone controller in accordance to the room temperature.
Configuration example of zone control |
|||
Variable |
Available options & Selection |
Note |
|
Activate temperature control type |
|||
Configuration > Functions > Function activation |
|||
Zone control |
| No | 1 Zone | 2 zones | 3 Zones | |
- |
|
Activate sensors & additional options |
|||
Configuration > Functions > Zone control |
|||
Zone control limitation |
| None | Interlock heating/cooling | |
Interlock zone heating and cooling with the main supply controller |
|
Temperature zone 1 > |
|||
Configure temperature zone |
|||
Configuration > Functions > Zone control > Temperature zone 1 |
|||
Name |
[Temperature zone 1] > Office |
Name the zone |
|
Original name |
Temperature zone 1 |
||
Temperature control mode |
| Supply air | Room cascade | | Extract air cascade | |
Supply temperature adjusted according to room temperature |
|
Type of heating |
| None | Water | Electric | |
Heater related settings |
|
Freeze protection |
| No | Yes | |
||
Pump control |
| No | Always running | Auto | |
||
Type of feedback |
| None | Alarm | Run indication | |
||
Digital start output |
| No | Yes | Yes with flow interlock | |
||
Heating output min limit |
[0] % |
||
Heating output max limit |
[100] % |
||
Type of cooling |
| None | Water | DX | |
Cooler related settings |
|
Pump control |
| No | Always running | Auto | |
||
Type of feedback |
| None | Alarm | Run indication | |
||
Digital start output |
| No | Yes | Yes with flow interlock | |
||
Cooling output min limit |
[0] % |
||
Cooling output max limit |
[100] % |
||
PID Settings |
|||
Configuration > PID controllers > Temperature zone 1 - Heating |
|||
P-band |
[10] oC |
Heater PID |
|
I-time |
[100] s |
||
D-time |
[0] s |
||
Configuration > PID controllers > Temperature zone 1 - Cooling |
|||
P-band |
[10] oC |
Cooler PID |
|
I-time |
[100] s |
||
D-time |
[0] s |
||
Configuration > PID controllers > Temperature zone 1 - Cascade |
|||
P-band |
[100] oC |
Room temperature controller PID |
|
I-time |
[300] s |
||
D-time |
[0] s |
||
Interface to the zone sensors and valves |
|||
Configuration > I/O allocation settings > Analog inputs |
|||
Supply air temperature zone 1 |
Any available input |
Zone temperature sensors |
|
Room air temperature zone 1 |
|||
Configuration > I/O allocation settings > Analog outputs |
|||
Heating zone 1 |
Any available output |
Valve control signals |
|
Cooling zone 1 |
|||
Operational settings |
|||
Data & Settings > Temperature control > Temperature zone 1 |
|||
Room air temperature zone 1 |
__ oC |
Actual room temperature |
|
Setpoint room |
[18.0] oC |
Desired room temperature |
|
Min limit supply air |
[12.0] oC |
Temperature limitations for the zone supply air |
|
Max limit supply air |
[30.0] oC |
||
Actual setpoint supply air |
__ oC |
Actual supply air temperature |
|
Operation overview |
|||
Data & Settings > Operation overview > Temperature zone 1 |
|||
Temperature control mode |
Room cascade |
Indication of selected control mode |
|
Room air temperature zone 1 |
__ oC |
Actual room temperature |
|
Setpoint room |
__ oC |
Desired room temperature |
|
Actual setpoint supply air |
__ oC |
||
Heating zone 1 |
__ % |
Valve control signals |
|
Cooling zone 1 |
__ % |
Chapter info