Access 5.x

Digital inputs


To simplify adaptation to external functions, all digital inputs can be configured to be either Normally open (NO) or Normally closed (NC).


The inputs are as standard normally open, i. e. if the input is closed, the function connected to the input is activated.


Be careful when changing the input from NO to NC since some digital functions can be configured to either NO or NC themselves. For example, you can choose if the Fire alarm input should be activated when it is closed or opened. Therefore, there is a risk that the signal is changed twice and the result is the opposite of the desired.



Allocate physical digital inputs

Configuration > I/O allocation settings > Digital inputs

Digital inputs

Device

Position

Feedback supply air fan

Controller

Select I/O

Feedback extract air fan

Controller

Select I/O

External alarm

Controller

Select I/O

...



Click on the name to enter settings. Adjust the name and change the default state of the input if necessary.

Select device used for this function. It can be either the Controller itself or one of the expansion modules.

Select the actual physical input used for this function.





Variable

Available options & Selection

Note


Rename and change the default state if necessary

Configuration > I/O allocation settings > Digital inputs > External alarm

Name

[External alarm] > [Alarm button]

Changeable name

Original name

External alarm

Unchangeable name

Contact function

| Normally open |

| Normally closed |

Normal state of digital input (circuit is open or closed)