To simplify adaptation to external functions, all digital inputs can be configured to be either Normally open (NO) or Normally closed (NC).
The inputs are as standard normally open, i. e. if the input is closed, the function connected to the input is activated.
Be careful when changing the input from NO to NC since some digital functions can be configured to either NO or NC themselves. For example, you can choose if the Fire alarm input should be activated when it is closed or opened. Therefore, there is a risk that the signal is changed twice and the result is the opposite of the desired.
Allocate physical digital inputs |
|||
Configuration > I/O allocation settings > Digital inputs |
|||
Digital inputs |
Device |
Position |
|
Feedback supply air fan |
Controller |
Select I/O |
|
Feedback extract air fan |
Controller |
Select I/O |
|
External alarm |
Controller |
Select I/O |
|
... |
|||
↓ |
↓ |
↓ |
|
Click on the name to enter settings. Adjust the name and change the default state of the input if necessary. |
Select device used for this function. It can be either the Controller itself or one of the expansion modules. |
Select the actual physical input used for this function. |
|
↓ |
|||
Variable |
Available options & Selection |
Note |
|
Rename and change the default state if necessary |
|||
Configuration > I/O allocation settings > Digital inputs > External alarm |
|||
Name |
[External alarm] > [Alarm button] |
Changeable name |
|
Original name |
External alarm |
Unchangeable name |
|
Contact function |
| Normally open | | Normally closed | |
Normal state of digital input (circuit is open or closed) |
|