Access 4.x

Control modes > Extract air cascade


Extract air temperature controller generates setpoint for the supply air temperature controller.


Settings and configuration for Extract air cascade control



Variable

Available options & Selection

Note


Activate temperature control type

Configuration > Functions > Function activation

Temperature control type

|...| Extract air cascade | … |

-


Activate sensors & additional options

Configuration > Functions > Temperature control

Extract air temperature sensor

|Yes | No |

-

Supply air temperature sensor

|Yes | No |

-


Configure inputs

Configuration > I/O allocation settings > Analog inputs >

Extract air temperature


Any available I/O

Supply air temperature



PI Settings

Configuration > PID controllers > Extract air

P-band

[100] oC

PI settings for the extract air controller

I-time

[300] s


Operational settings

Data & Settings > Temperature control > Supply air controller

Supply air temperature

__ oC

Actual supply air temperature

Min limit supply air

[12.0] oC

Limits of the supply air temperature. Temperature off these limits will trigger alarm AL-88 or AL89

Max limit supply air

[30.0] oC

Actual setpoint supply air

__ oC

Dictionary

Data & Settings > Temperature control > Extract air controller

Extract air temperature

__ oC

Actual extract air temperature

Setpoint adjustment

[0] oC

Dictionary

Setpoint extract air

[20.0] oC

Setpoint

Actual setpoint extract air

__ oC

Dictionary



Related topics:

Temperature controllers

Summer/Winter mode