Access 4.x

Control modes > Room (summer) else supply air

This temperature control mode combines Room cascade and Supply air outdoor compensated modes.

Summer/winter mode function is utilized for switching.


In summer - room cascade mode is active and room temperature controller generates the setpoint for the supply air temperature controller.

In winter - supply air outdoor compensated mode is active. Setpoint for supply air temperature is determined by outdoor temperature and dependency curve.



Settings and configuration for Room (summer) else supply air control



Variable

Available options & Selection

Note


Activate temperature control type

Configuration > Functions > Function activation

Temperature control type

|...| Room (summer) else supply air | … |

-


Activate sensors & additional options

Configuration > Functions > Temperature control

Room temperature sensor

| No | 1 | 2 | 3 | 4 |

-

Calculation mode room temperature

| Average | Min value | Max value | Weighted average |

* Option available if the number of room temperature sensors is more than 1.

Weighted average - average of the min and the max values

Supply air temperature sensor

|Yes | No |

-

Summer/Winter mode

|Yes | No |

Function switches to | Yes | automatically in this control mode

Type of switch summer/winter

| Calendar | Changeover | Digital input | Outdoor temperature |

[Outdoor temperature] is the default option


Configure inputs

Configuration > I/O allocation settings > Analog inputs >

Room temperature 1


Any available I/O

Supply air temperature



PI Settings

Configuration > PID controllers > Room

P-band

[100] oC

PI settings for the room controller

I-time

[300] s


Operational settings

Data & Settings > Temperature control > Supply air controller

Supply air temperature

__ oC

Actual supply air temperature

Setpoint outdoor curve

>

Setpoint curve for winter

Neutral zone (C°)

[0.0] oC

Width of neutral zone

Min limit supply air

[12.0] oC

Limits of the supply air temperature. Temperature off these limits will trigger alarm AL-88 or AL89

Max limit supply air

[30.0] oC

Actual setpoint supply air

__ oC

Dictionary

Data & Settings > Temperature control > Room controller

Room temperature

__ oC

Actual room temperature

Setpoint room

[21.0] oC

Setpoint for summer

Outdoor temp for switch between summer/winter

[13.0] oC

Summer / winter mode switch settings

Outdoor temp hysteresis for switch between summer/winter

[1.0] oC

Actual setpoint room

__ oC

Dictionary






Curve point

Outdoor temperature (C°)

Setpoint supply temperature (C°)


Setpoint outdoor curve

Data & Settings > Temperature control > Supply air controller > Setpoint outdoor curve

Point 1

[-20] oC

[22] oC

Point 2

[5] oC

[20] oC

Point 3

[20] oC

[20] oC

Point 4

[30] oC

[22] oC





Setpoint outdoor curve




Related topics:

Temperature controllers

Neutral zone

Summer/Winter mode


Chapter info                              

Last reviewed: 9/16/2021