Control modes > Extract air outdoor compensated |
The extract air temperature setpoint is outdoor temperature compensated using a control curve with 4 node points.
Settings and configuration for Extract air outdoor compensated control |
|||
Variable |
Available options & Selection |
Note |
|
Activate temperature control type |
|||
Configuration > Functions > Function activation |
|||
Temperature control type |
|…| Extract air outdoor compensated |...| |
- |
|
Activate sensors & additional options |
|||
Configuration > Functions > Temperature control |
|||
Extract air temperature sensor |
|Yes | No | |
- |
|
Supply air temperature sensor |
|Yes | No | |
- |
|
Configure inputs |
|||
Configuration > I/O allocation settings > Analog inputs > |
|||
Extract air temperature |
Any available I/O |
||
Supply air temperature |
|||
PI Settings |
|||
Configuration > PID controllers > Extract air |
|||
P-band |
[100] oC |
PI settings for the extract air controller |
|
I-time |
[300] s |
||
Operational settings |
|||
Data & Settings > Temperature control > Supply air controller |
|||
Supply air temperature |
__ oC |
Actual supply air temperature |
|
Min limit supply air |
[12.0] oC |
Limits of the supply air temperature. Temperature off these limits will trigger alarm AL-88 or AL89 |
|
Max limit supply air |
[30.0] oC |
||
Actual setpoint supply air |
__ oC |
||
Data & Settings > Temperature control > Extract air controller |
|||
Extract air temperature |
__ oC |
Actual extract air temperature |
|
Setpoint adjustment |
[0] oC |
||
Actual setpoint extract air |
__ oC |
||
Setpoint outdoor curve |
> |
Setpoint curve |
|
Curve point |
Outdoor temperature (C°) |
Setpoint extract air temperature (C°) |
|
Setpoint outdoor curve |
|||
Data & Settings > Temperature control > Extract air controller > Setpoint outdoor curve |
|||
Point 1 |
[-20] oC |
[22] oC |
|
Point 2 |
[5] oC |
[20] oC |
|
Point 3 |
[20] oC |
[20] oC |
|
Point 4 |
[30] oC |
[22] oC |
|
Setpoint outdoor curve |
|||