Humidity compensation configuration example


The “Humidity Setpoint Compensation” sequence is designed to be used in combination with the Dehumidification function. During humidity control processes, the supply-air temperature may drop below the acceptable minimum limit even when the reheater is already operating at full capacity (100%). In such cases, the Humidity setpoint Compensation sequence helps restore the required temperature by counteracting the output of the humidity control function. The output (actual setpoint) of the humidity control function is proportionally reduced to increase the supply-air temperature.

The Humidity Setpoint Compensation sequence should be configured with a higher order number for Heating than the After Heater function.

Example:
Configuration > Functions > Function Activation > Heating/Cooling Sequence Setup

Position

Function

Function Name

SEQ-A

Heating (2)

Heating (After heater)

SEQ-B

Heating (1)

Exchanger

SEQ-F

Heating (3)

Humidity Setpoint Compensation



Humidity setpoint compensation




Variable

Available options & Selection

Note


Sequence selection

Configuration > Functions > Function activation > Heating/Cooling sequence setup

Sequence for heating

|...| SEQ-F Fan setpoint compensation |...|



Sequence settings

Configuration > Functions > Function activation > Heating/Cooling sequence setup > Fan setpoint compensation

Name

[Fan setpoint compensation] >

> [Humidity setpoint compensation]

Rename the sequence

Type of sequence

|Cooling | Exchanger | Heating | Damper | | Fan setpoint compensation | Humidity setpoint compensation |

Choose the correct sequence type

Digital start output

| No | Yes |

Standard settings of sequence can be adjusted if needed

Sequence output when recirculation/support

| 0% | 100% | Auto |

Sequence output min limit

0%

Sequence output max limit

100%

Sequence output when the unit is stopped

0%


PID Settings

Configuration > PID controllers > Humidity setpoint compensation

P-band

[10] oC

PID settings for the sequence

I-time

[100] s

D-time

[0] s


Compensation limit

Data & Settings > Temperature control > Humidity setpoint compensation

Max humidity compensation

[100] %RH

Maximum allowed adjustment of Humidification and Dehumidification setpoints