Access allows override control of the selected sequence (typically the cooling sequence) to enable dehumidification of the supply air through condensation. During this mode, the dehumidification function overrides the cooling signal from the temperature controller, allowing the output to activate even when there is no cooling demand. The dehumidification output increases as the room or extract-air humidity rises.

Starting from Access version 5.4, the dehumidification function has been enhanced with a dew-point control feature. When enabled, dehumidification will only activate if the dew point can be reached. To enable dew-point calculation and control, three new configuration parameters have been introduced:

  • Cooler capacity (kW)
  • Cooler inlet air temperature
  • Cooler inlet air humidity

To reheat the dehumidified (dried) air, the reheater is used. However, in some cases, reheating alone may not be sufficient, and the supply-air temperature may drop below acceptable limits. To prevent this, a compensation algorithm can be activated. When the after-heater operates at maximum capacity, this algorithm allows the temperature controller to counteract the humidity controller by reducing the dehumidification demand, thus maintaining an acceptable supply-air temperature.

To enable this compensation control, the Humidity Setpoint Compensation sequence must be activated.


Configuration example of the dehumidification (sequence "SEQ-C Cooling")


Variable

Available options & Selection

Note


Activate Humidity control

Configuration > Functions > Function activation

Humidity control

... | Dehumidification |…



Configure function

Configuration > Functions > Humidity control

Humidity control

 Dehumidification

Indication of what function has been activated

Select sequence for dehumidify

... | Cooling |...

Sequence to be used for dehumidification

Block dehumidification when dew point not reached

| No | Yes |

Default | No|

The settings bellow are only available if selected | Yes |

Capacity of cooler

[0] kW


Cooler inlet air temperature

| Cooler inlet air temperature | Efficiency temperature exchanger | Outdoor temperature |

Choose sensors to measure temperature and humidity of the air entering the cooling coil

Cooler inlet air humidity

| Cooler inlet air humidity | Humidity outdoor |


PID Settings

Configuration > PID controllers > Dehumidification

P-band

[100] %RH

PID settings for dehumidification signal

I-time

[300] s

D-time

[0] s

PID output max limit

[100] %

max output of the PID can be limited


Hardwired interface

Configuration > I/O allocation settings > Analog inputs >

Humidity room/extract air

Any available I/O


Cooler inlet air temperature

Cooler inlet air humidity


Operational settings

Data & Settings > Humidity control

Humidity room/extract air

__ %

Actual measured RH

Setpoint humidity room/extract

[50] %RH



Operation overview

Data & Settings > Operation overview > Humidity

Humidity room/extract air

__ %

Overview of the function in action

Setpoint humidity room/extract

[50] %RH

Humidity control

__ %

Humidity control mode

Not active | Dehumidification

Calculated lowest temperature - cooling capacity

__oC

Dewpoint cooler - start condensation

__oC

Cooler inlet air temperature

__oC

Cooler inlet air humidity

__ %RH

Data & Settings > Operation overview > Cooling


Cooling (SEQ-C)

__ %

Overview of the performance of the sequence

Cooling start (SEQ-C)

Off | On

Cooling pump (SEQ-C)

Off | On