The described functions may be used only in compliance with applicable local regulations. Compliance must be verified by the user or confirmed with the local Systemair organization.
The Fire/Smoke mode can be activated via a dedicated digital input or the specialized “T1 SMOKE” input.
The T1 SMOKE input monitors the current passing through the connected smoke detector, and the controller responds based on the measured value. Four operating states are defined according to the measured current:
Normal
Service
Alarm
Error
The specific current thresholds depend on the smoke detector model. These values are factory-tested, predefined in the controller, and cannot be adjusted manually.
If the measured current deviates from the normal operating range, an alarm may be triggered depending on the detected condition:
6015 – Smoke Alarm: Smoke detected
6020 – Service Alarm: Smoke detector requires service
6025 – Sensor Error: Smoke detector fault
Use example of T1 Smoke input |
|||
Variable |
Available options & Selection |
Note |
|
Configuration of the smoke function |
|||
Configuration > Functions > Fire/Smoke |
|||
Fire function |
> |
Setup of the Fire function |
|
Smoke function |
> |
Setup of the Smoke function |
|
Smoke detector function |
| Off | |
The T1 SMOKE will be used to activate Smoke mode |
|
| Fire alarm | |
|||
| Smoke alarm | |
|||
Smoke detector brand |
| Calectro | Finsecure | |
Select smoke detector in use |
|
Smoke alarm digital input |
| No | Yes | |
In addition to T1 SMOKE the digital input can also be used to trigger this mode |
|
Status of the smoke alarm |
|||
Data & Settings > Fire/Smoke |
|||
Smoke detector status |
Error / Alarm / Service / Normal |
Based on the measured current |
|
Related topics:
Calectro UG-3-O (external link)