Sum alarm indication activates digital output in case of active alarms of the particular alarm class. Two digital outputs for the alarm class indication are available:
- DO: Sum alarm 1 - indication of the A class alarms / indication A and B class alarms
 - DO: Sum alarm 2 - indication of the B class alarms / indication B and C class alarms
 
Sum alarm indication is reset once the active alarms are acknowledged.
Example of setting sum alarm indication  | 
|||
Variable  | 
Available options & Selection  | 
Note  | 
|
Activating Sum alarm indication  | 
|||
Configuration > Functions > Extra indications & outputs  | 
|||
Sum alarm outputs  | 
| No |  | 
-  | 
|
| A/B-alarm |  | 
Sum alarm 1 for A or B class alarms  | 
||
| A-alarm + B-alarm |  | 
Sum alarm 1 for A class alarms Sum alarm 2 for B class alarms  | 
||
| A-alarm + B/C-alarm |  | 
Sum alarm 1 for A class alarms Sum alarm 2 for B and C class alarms  | 
||
IO allocation  | 
|||
Configuration > I/O allocation settings > Digital outputs  | 
|||
Sum alarm 1  | 
Any available I/O  | 
Indicating A class alarms  | 
|
Sum alarm 2  | 
Indicating B and C class alarms  | 
||
Related topics