Access 4.x

Control modes > Supply air


The supply air temperature is kept at the fixed setpoint (setpoint compensation can apply).


Settings and configuration for Supply air control



Variable

Available options & Selection

Note


Activate temperature control type

Configuration > Functions > Function activation

Temperature control type

| Supply air | … |

-


Activate sensors & additional options

Configuration > Functions > Temperature control

Supply air temperature sensor

|Yes | No |

-


Configure input

Configuration > I/O allocation settings > Analog inputs >

Supply air temperature


Any available I/O


Operational settings

Data & Settings > Temperature control > Supply air controller

Supply air temperature

__ oC

Actual supply air temperature

Setpoint supply air

[18.0] oC

Setpoint

Neutral zone (C°)

[0.0] oC

Width of neutral zone

Setpoint adjustment

[0] oC

Dictionary

Min limit supply air

[12.0] oC

Limits of the supply air temperature. A temperature below or above these limits will trigger alarm AL-88 or AL89

Max limit supply air

[30.0] oC


Related topics:

Temperature controllers

Neutral zone

Summer/Winter mode