Access 4.x

Control modes > Supply air outdoor compensated


The supply air temperature setpoint is outdoor temperature compensated using a control curve with 4 node points.


Settings and configuration for Supply air outdoor compensated control


Variable

Available options & Selection

Note


Activate temperature control type

Configuration > Functions > Function activation

Temperature control type

|...| Supply air outdoor compensated |...|

-


Activate sensors & additional options

Configuration > Functions > Temperature control

Outdoor temperature sensor

| No | Intake | Outdoor | Outdoor + Intake air |

-

Supply air temperature sensor

|Yes | No |

-


Configure inputs

Configuration > I/O allocation settings > Analog inputs >

Outdoor temperature

Any available I/O


Supply air temperature


Operational settings

Data & Settings > Temperature control > Supply air controller

Supply air temperature

__ oC

Actual supply air temperature

Setpoint outdoor curve

>

-

Neutral zone (C°)

[0.0] oC

Width of neutral zone

Setpoint adjustment

[0] oC

Dictionary

Min limit supply air

[12.0] oC

Limits of the supply air temperature. Temperature off these limits will trigger alarm AL-88 or AL89

Max limit supply air

[30.0] oC

Actual setpoint supply air

__ oC

Dictionary






Curve point

Outdoor temperature (C°)

Setpoint supply temperature (C°)


Setpoint outdoor curve

Data & Settings > Temperature control > Supply air controller > Setpoint outdoor curve

Point 1

[-20] oC

[22] oC

Point 2

[5] oC

[20] oC

Point 3

[20] oC

[20] oC

Point 4

[30] oC

[22] oC





Setpoint outdoor curve



Related topics:

Temperature controllers

Neutral zone