Access 5.x |
Control modes > Extract air cascade |
Extract air temperature controller generates setpoint for the supply air temperature controller.
Settings and configuration for Extract air cascade control |
|||
Variable |
Available options & Selection |
Note |
|
Activate temperature control type |
|||
Configuration > Functions > Function activation |
|||
Temperature control type |
|...| Extract air cascade | … | |
- |
|
Activate sensors & additional options |
|||
Configuration > Functions > Temperature control |
|||
Extract air temperature sensor |
|Yes | No | |
- |
|
Supply air temperature sensor |
|Yes | No | |
- |
|
Configure inputs |
|||
Configuration > I/O allocation settings > Analog inputs > |
|||
Extract air temperature |
Any available I/O |
||
Supply air temperature |
|||
PI Settings |
|||
Configuration > PID controllers > Extract air |
|||
P-band |
[100] oC |
PI settings for the extract air controller |
|
I-time |
[300] s |
||
Operational settings |
|||
Data & Settings > Temperature control > Supply air controller |
|||
Supply air temperature |
__ oC |
Actual supply air temperature |
|
Min limit supply air |
[12.0] oC |
Limits of the supply air temperature. |
|
Max limit supply air |
[30.0] oC |
||
Actual setpoint supply air |
__ oC |
||
Data & Settings > Temperature control > Extract air controller |
|||
Extract air temperature |
__ oC |
Actual extract air temperature |
|
Setpoint adjustment |
[0] oC |
||
Setpoint extract air |
[20.0] oC |
Setpoint |
|
Actual setpoint extract air |
__ oC |
Related topics: